 CHEAPEST MODIFIED SINE WAVE INVERTER WITH CHARGER AND AVR function.

 

MODEL
(Any Power Quasa Series)
12/24VDC Series
 
0.6KW ~ 1.0KW
Line Mode Specifications:
Input Voltage Waveform
Sinusoidal (Utility or Generator)
Any-Power Solution AVR Function
LV (NA/JPN)
HV (INTL)
Acceptable Input Voltage Range (Vac)
0-160
0-300
Nominal Input Voltages (±4% Vac) 
100
110
120
220
230
240
(A) Line Low loss N/W (On Battery)
75
81
89
168
176
183
(B) Line Low comeback N/W (On Boost)
80
84
92
178
186
193
(C) Line 2nd boost threshold (On Boost)
**
**
**
**
**
**
(D) Line 2nd boost comeback (On Boost)
**
**
**
**
**
**
(E) Line 1st boost threshold (On Boost)
90
99
108
198
207
216
(F) Line 1st boost comeback (On Normal)
93
102
112
205
215
225
(G) Line buck comeback (On Normal)
106
118
128
235
246
256
(H) Line buck threshold (On Buck)
110
121
132
242
253
264
(I) Line high comeback (On Buck)
115
131
142
253
266
278
(J) Line high loss (On Battery)
120
134
145
263
276
288
 
Nominal Input Frequency
50Hz / 60Hz (Auto detection)
Low Line Frequency Re-connect
45Hz ± 1Hz(50Hz) /55Hz± 1Hz(60Hz)  
Low Line Frequency Disconnect
47Hz ± 1Hz(50Hz) /57Hz± 1Hz(60Hz)  
High Line Frequency Re-connect
55Hz ± 1Hz(50Hz) /65Hz± 1Hz(60Hz) 
High Line Frequency Disconnect
53Hz ± 1Hz(50Hz) /63Hz± 1Hz(60Hz)  
Output Voltage Waveform
As same as Input Waveform
Over-Load Protection 
Circuit breaker & Software
Output Short Circuit Protection
Circuit breaker & Software
Efficiency (Line Normal Mode)
>95%
Transfer Time 
6~8ms Typical, 10ms Max
Invert Mode Specifications:
MODEL POWER TYPE
Any Power Quasa Series
 
APQ 0612 ~ 1024/E
Output Voltage Waveform
Step Sine Wave
Rated Output Power 
0.6 ~ 1.0KW
Power Factor
0~1.0
Nominal Output Voltage (V)
100-110-120Vac
220-230-240Vac
Nominal Output Frequency (Hz) (Default)
60Hz
50Hz
 
Auto Tracking Main Frequency (First Connection)
Output Voltage Regulation
±10% RMS
Nominal Efficiency
>80%
Line Mode (in VA)
>120%+/-15% of rated SPS load, overload alarm, 
and fault after 3 Minutes.
<100% of rated SPS load, overload alarm release.
 
>150% +/-15% of rated SPS load, immediately fault
Battery Mode (in Watt)
>120% +/-15% of rated SPS load, overload alarm, 
and S.D after 10 Seconds.
<100% of rated SPS load, overload alarm release.
 
>150% +/-15% of rated SPS load, immediately S.D
Capable of Starting Electric Motor
1HP
Output Short Circuit Protection
Current Limit Function (Fault after 1sec)
Bypass Breaker Size
12A
Nominal DC Input Voltage
12.0Vdc
24.0Vdc
Min DC Start Voltage
10.0Vdc
20.0Vdc
Low Battery Alarm
10.5Vdc
21.0Vdc
Low DC Input Shut-Down
10.0Vdc
20.0Vdc
High DC Input Alarm & Fault
16.0Vdc 
32.0Vdc
High DC Input Recovery
15.5Vdc
31.0Vdc  
AUTO-RESTART
INV will auto-restart 
Input line restores and battery voltage > 11.0Vdc.
Charge Mode Specifications:
MODEL Battery Type
(Any Power Quasa Series)
12VDC Series
24VDC Series
 
0.6 ~ 1.0KW
Nominal Input Voltage
100-110-120Vac
220-230-240Vac
Nominal Output Voltage
13.8Vdc +/-1.5%
27.6Vdc +/-1.5%
Nominal Charge Current (Amp)
20Amp Max
10Amp Max
Input Breaker Size 
10/20Amp
Over Charge Protection
Bat. V ≥15.7Vdc
Beeps 0.5s every 1s & fault after 60s
Charger Algorithm
Three stage: 
→Boost CC    (Constant Current Stage) 
 → Boost CV   (Constant Voltage Stage) 
  → Float      (Constant Voltage Stage)
Indicator & Audible Alarm     
LED
Battery Charger
(Shore power on)
GREEN LED Lighting On Battery Charger Mode
 
Inverter
(Inverter power on)
GREEN LED Lighting On Inverter Mode
 
Alarm
(Check alarms on box)
RED LED Lighting On Alarm
Switch
Unit Power Off
Power Totally Off
 
Unit Power On
Power On  
Battery Voltage Low
Inverter Green LED Lighting, and the buzzer beep every 5s.
Battery Voltage High
Inverter Green LED Lighting, and the buzzer beep every 1s.
Invert Over-Load
Inverter Red LED Lighting, and the buzzer beep every 0.5s.
Over Temperature
Inverter Red LED Lighting, and the buzzer beep every 1s.
Fault
Inverter Red LED Lighting, and the buzzer beep continuously.
Protection
Over Temp. Protection
Heat sink temp. ≥105ºC, Fault (shutdown Output) after 30 seconds
Back-Feed Protection 
Yes
Fault Recovery
By Restart The INV.
FAN Operation
Fan Operation
· Fan should not start/stop suddenly.
· Fan should run at minimum speed needed to cool unit.
· Fan noise level target <50db.
The Fan Logic as Below:
Condition
Fan Speed Status
Transfer Point
HEATSINK TEMPERATURE
Half >>> Full
T ≥ 85℃
Full >>> Half
T ≤ 80℃
 
General Specifications
Safety Certification
CE (EN62040-1)
EMC Classification
EN62040-2, C2 
Operating Temperature Range
0°C to 40°C
Storage temperature
-15ºC to 60ºC
Operation humidity
5% to 95%
Audible Noise
60dB max
Cooling
Forced Air, Variable Speed Fan
Size
APQ 0.6~1.0KW :  285mm* 145mm* 145mm;