Product Main

Specifications

avr vr6
Input:
Voltage, rated                     120 V  240 V
Voltage, limits                90-140 V   180-280 V
Frequency                   50-240 Hz  50-240 Hz
Burden (at rated V)         1440 VA  2400 VA 
Output:
Voltage, continuous           65 Vdc  125 Vdc
Voltage, forcing 10 sec.   100 Vdc  200 Vdc
Current, continuous           12 Adc  10 Adc
Current, forcing 10 sec.     25 Adc  20 Adc
Min. feld resistance          4 Ohms  10 Ohms 
Sensing: 100 to 120 V +/-10% with standard 10K Ohm control, 1 phase or 3 phase, 50/60 or 400 Hz;
Paralleling: 1 A or 5 A for 6% droop maximum; 10 VA maximum burden;
Regulation accuracy: +/- 0.5% maximum;
Under frequency protection breakpoints: Adjustable 45 to 65 Hz;
Regulator response: Less than 4 milliseconds;
Thermal stability: Less than 0.5% per 40° ambi-ent temperature change;
 Power dissipation: Less than 50 W at maximum continuous rating;