Main Features |
|
Intelligent full digital controlled design |
|
Using full digital controlling technology makes UPS detection, response, protection more accurate and speedy,which greatly upgrade UPS systems reliability. |
|
Comprehensive function and reliable power protection |
|
Real time self check and adjustment, strengthen the UPS protection; |
|
True online double conversion design with isolation transformer, guarantee the high reliability; |
|
Industrial power supply,galvanic isolation ,resist to cold load pickup, good dynamic response; |
|
Settable inner parameters and adjustment, more suitable to user environments. |
|
|
|
Intelligent battery management system, greatly reduce the input cost |
|
Intelligent full bridge rectifier& charger with softstart function and the protection of phase dislocation, phase lack,over voltage, under voltage, over current. Achieving battery auto monitoring,maintenance,management, auto transfer between floating charge and quick charge, ensuring battery life time with most reasonable charge mode. |
|
Real time monitor and adjust charge mode, auto transfer the charge mode and features with charging current compensation, auto adjust charging current; |
|
Periodic test and calculate the battery capacity, tell the battery backup time,send the fault messages in time for each battery fault; |
|
Battery wrong connection and voltage abnormal protection; |
|
Compatible with various generators, cutting down the UPS running cost. |
|
Monitoring and network management upgrade the UPS power protection |
|
RS232 port and SNMP card make UPS possible to realize monitoring and network communications,Monitoring operation can also be achieved by using dry contact. |
|
Humanization design of UPS structure, more closer to users |
|
Easy to maintain and simple to install; |
|
Intelligent cooling fan thermal solution; |
|
4×12 characters LCD backlight display, more than 200 messages of events, data and history. |
|
Specification |
|
|
|
Model |
|
Capacity VA/Watts: |
RP100L33/8KW,RP150L33/12KW,
RP200L33/16KW, RP300L33/24KW, RP400L33/32KW (Long Run UPS w/o battery,parallel redundancy) |
Rectifier |
|
Phase: |
Three Phase input/three phase output |
Input: |
3×380Vac+N+W |
Voltage range: |
320~480Vac |
Frequency: |
45-65 Hz |
Inverter features |
|
Voltage range: |
3X380Vac+N+W |
Voltage stability: |
380±1%(static load); 380±2%(50~0% load change); 380±3%(100~0% load change) |
Frequency stability: |
50Hz±0.1% |
Waveform: |
Pure sine wave |
Distortion: |
<1%(Full linear load);<3%(100~0%load change) |
Power factor: |
0.8 |
Overload: |
>120% for normal bypass ; >150% for 10 minute bypass or shut down |
Crest ratio: |
3∶1 |
Load unbalance: |
Three phase load 100% unbalance |
Voltage unbalance: |
≤1% (Balance load); ≤2%(50% unbalance load) |
Phase displacement: |
≤1° (Balance load); ≤2°(50% unbalance load) |
General features |
|
Efficiency: |
>92% |
Switching time: |
0ms |
Noise suppressor: |
<55~65dB(At 1 meter) |
Working temperature: |
-10- 40℃ |
Environment umidity: |
<95% Non-condensing |
Safety standard: |
EN50091-1/IEC950 |
Parallel redundancy: |
Connect up to 6 units in parallel |
EMC standard: |
EN50091-2 |
Generator compatible: |
Yes |
Protection: |
Overload, short circuit, over temperature, mains over/under voltage, Battery over/under voltage |
Display: |
LCD (4X12 in English & Chinese, event log with 112 messages)+LED |
DC starts |
Yes |
Battery features |
|
Type: |
Maintenance-free sealed lead-acid |
Floating Voltage: |
405Vdc |
Battery Voltage: |
360Vdc (32Pcs 12Vdc) |
Bypass |
|
Static bypass input: |
380 Vac±15% |
Static bypass ransfer: |
0ms |
Frequency tracking rate: |
1Hz/sec or 5Hz/sec (optional) |
Frequency range: |
±2%, 4%, 6%(optional) |
Static bypass overload: |
200%~5 minutes; 1000%~10 seconds |
Manual Bypass: |
Yes |
Communication terface |
Comconnect: |
True RS-232 communication port, Dry contact/RS485/SNMP card |
Monitor software: |
Various operating systems supported |
Physical parameter |
Dimension(WxDxH): |
430X1030X985 |
Weight (Kg): |
RP100L33/217,RP150L33/230,RP200L33/250, RP300L33/288,RP400L33/340 |
|