three Phase 380V Large LCD Graphical display panel online High Frequency UPS with RS232, AS400
Key Features
● Large LCD Graphical display panel, convenient for operate
● Advanced IGBT rectification, Input power factor: 0.99
● Input current harmonic < 3%
● The Efficiency of the machines is as high as 94%
● Connect up to 8 units in parallel for maximum flexibility (no parallel kit required), and compatible to battery share in the parallel mode, which helps the customers to extend the system capacity with lowcost.
● Intelligent management of battery charging and discharging.
● Twin-Chiannel line input.
● Large LCD Graphical display panel, convenient for operation.
High-efficient, energy saving, green environmental protection
The efficiency of the machines is as high as 94% and reaches over 98% in the ECO mode which can help to reduce the power loss of UPS. IGBT FM intelligent rectifier and inverter technology, the input power factor is as high as 0.99 input current harmonic wave (THDI) is as low as 3%
Application:
Small and medium-sized data centers, Network management center, Computer rooms for enterprises, , Control center for Manufacture, Transportation, Energy source etc. field, And for industrial precision production and test equipment(like SMT, AI equipment), As power supply & protect‘s
key equipment
Technical Specifications of Online UPS HP9330C 20-80KVA
Model |
HP9330C 20-80KVA |
||||||
20K |
20K-XL |
30K-XL |
40K-XL |
60K-XL ISO |
80K-XL ISO |
||
Rated Capacity |
20KVA/16KW |
30KVA/24KW |
40KVA/32KW |
60KVA/48KW |
80KVA/64KW |
||
Rated Voltage |
380/400/415VAC Three-phase 4 line + earth line |
||||||
Rated Frequency |
50/60HZ |
||||||
Input |
|||||||
Voltage range |
380VAC±25% |
||||||
Frequency range |
50/60HZ±5% |
||||||
Wiring |
Twin- channel line input |
||||||
THDI |
<3% |
||||||
Power factor |
>0.99 |
||||||
Output |
|||||||
Voltage precision |
380VAC (±1%); Three-phase 4 line + earth line |
||||||
Frequency precision |
50/60HZ±0.2% |
||||||
Power factor |
0.8 |
||||||
Current crest ratio |
3∶1 |
||||||
Overload capacity |
≤110%for 60 minutes; ≤125%for 10min; ≤150%for 1min; |
||||||
Battery |
|||||||
Charging current |
0.5~4.5A(adjustable) |
||||||
Backup time |
7mins |
Determined by the amount of external-connected cells |
|||||
Quantity |
28/30/32(selective); compatible to battery share in the parallel mode |
||||||
Efficiency
|
|||||||
Line mode/BAT mode |
94% |
||||||
ECO mode |
98% |
||||||
Indication |
|||||||
LCD |
I/O voltage, current, frequency, BAT voltage, charging current value, discharging current value, fault display, fault, warning |
||||||
Communications |
|||||||
Communication interface |
RS232, AS400, RS485, Service, EPO, BAT temperature compensation, Intelligent Slot , SNMP(Option) |
||||||
Operation Environment |
|||||||
Temperature |
0~40℃ |
||||||
Humidity |
0~95% (no dewfall) |
||||||
Storage temperature |
-25℃~55℃ |
||||||
Altitude(M) |
< elevation 1500m |
||||||
Weight |
|||||||
weight(KG) |
Net weight |
182.5 |
82 |
110 |
114 |
282 |
306 |
Gross weight |
204 |
122 |
160 |
164 |
356 |
380 |
|
Dimension(WXDXH)mm |
420X630 X1240 |
420X630 X950 |
490X680 X1180 |
600 X800 X1850 |
Follow standard of GB/IEC regulation: EMC:GB7260.2/IEC62040-2 GB/17626.2~5/IEC61000-4-2~5 SAFETY:GB4943
Note: Product specifications are subject to change without further notice