Product Main

Specifications

Three phase four wires 40-70Hz Online HF UPS, 10 - 40KVA 3 Phase in / out 190vac / 208vac / 220Vac

 

POWERWELL (America) seriesOnline HF UPS 10-40kva,3-3phase 190vac / 208vac / 220Vac ;

HRD Powerwell  (America) series three phase UPS offers advanced technology that increase performance and reliability.3nos high speed DSPs with completed digital control fully to  ensure high quality of power supply,high input power factor makes UPS green energy saving power.it also offers humanization design:full front access of service ability,user-friendly interface.

 

Technical Specifications:

 

Model

PWA3310

PWA3315

PWA3320

PWA3330

PWA3340

Capacity/Rating Power

10KVA/8KW

15KVA/12KW

20KVA/16KW

30KVA/24KW

40KVA/32KW

 

 

 

 

AC Input 

 

 

 

Rated voltage

190/208/220Vac(Line-Line)

Input connection

Three phase four wires

Power factor

Above 0.99

THDI 

Less 5%

Voltage range 

150-270Vac or 280-480Vac(Line voltage)

Frequency 

40-70Hz

Bypass     

150-270Vac or 280-480Vac(Line-Line)+/- 15%

 

 

 

 

 

Output

 

 

 

 

voltage precision

±0.5%

Dynamical

voltage transient

Less 5% ( 0~100% load step)

THDU

THD less 3%( linear load ),5%(non-linear load)

Power factor

0.8 (lag)

Frequency

tracking range

50/60Hz±3Hz

Frequency precision

 

±0.05%(Battery mode) , ±3hz(Line mode)

 

 

 

 

 

OUTPUT

 

phase displacement

120±0.5°(Balance or imbalance load )

Frequency

tracking rate

Less 1Hz/s

 

Overload capability

105% long time operation

125%,transfer to bypass after 10 minutes

Above 150%, transfer to bypass after 1s

 

 

Bypass

overload

Above 180%, long time operation

Above 180%, last for 1s

Transfer time

0ms

System

System efficiency 

Above 90%;98%(ECO) mode

Display 

 Touch screen LCD+LED

 

 

EMC

IEC62040-2

IEC61000-4-2 (ESD)

IEC61000-4-3 (RS)

IEC6100-4-4 (EFT)

IEC6100-4-5 (Surge)

Noise (1m)

Less 60dB

Insulating resistance

Above 2M (500VDC)

Insulating intensity

(input, output to PE) 2820Vdc, leakage current lower than 3.5mA, no flashover in 1min

Surge protection

Meet the requirement of IEC60664-1class,endure surge of 1.2/50us+8/20us higher than 6KV/3KA

IP class

IP30

Battery configuration

Installation(dc)

+192/216/240Vdc ,﹣192/216/240Vdc

Connection

Bottom cable connection in front

Charger

20% Power capacity(DSP controlled ,adjustable)

Dimension (W×D×H)mm

620×800×1350(or inbuilt bat.)

720×900×1450

Weight (without battery)

230Kg/(310kg)

280kg

Application: ISP(Internet Service Provider),IDC(Internet Data Center),computing center,bank,server center,precise equipment and etc. 

 

Perfect Applications:

Internet Servor ,Internet Data Center), Medium-scale network system / computingcenter, bank and securities, business server group, Medium-scale office automation,precision equipment, etc.

Features: complete digital control technology

Fully digital control with two DSPs, all the subsystems are digital controlled including the IGBT rectifier, inverter, charger, discharger.

Excellent electrical properties

True online double conversion instruction offers the safe and effective power protection for various loads, with strong output load capacity;

High input power factor, green and energy-saving

Input end with PFC and input PF of the whole UPS up to 0.99;

Strong environmental adaptability 

Wide input voltage and frequency range, adaptation to all kinds of climatic

and geographical environment;

Comprehensive protection measures 

 Surge Protection, short circuit protection, and other protection to ensure the reliability of UPS;

IGBT and SCR adopts the advanced EUPEC power module;

The adoption of advanced technology (IGBT driving technology, IGBT soft over-current shutdown) improves the reliability and safety of inverter.

Similar modular design

Each phase main board are designed like rack  for easy assembling and maintenance

Intelligent battery management 

Adopting the intelligent battery management, prolonging the using life

of battery,decrease the maintaining work;

The max battery charging current can set by end users according to the

battery features, to avoid any damage caused by the big charging current;

Periodic self-test battery, detecting the battery problems timely;

With battery over voltage / current protection, to protect the battery;

Cold start and Mains start Function

Directly start the UPS through battery or start UPS through Mains only.

Superior network monitoring capabilities 

Communication port (RS232, USB, and so on) connecting with computer,SNMP card optional,

Easy-maintenance design

a) Adopts the full front maintenance design, reducing the restrictions

on the installation space, and saving the space of computing center;

b)Modular design class, convenient and easy site maintenance;

c) With manual maintain bypass,

d)Battery replacement without disrupting the UPS running;

e) Historical records search function, events up to1,000 items;

Friendly interface

 LargeLCD display and LED status indication; Abundant information display of UPS;