High output power factor 60KVA Online Low Frequency UPS GP9330C Series with LBS function
Key Features
1. Advanced operation mode
2. DSP control
3. Double CPU control
4. Modularize
5. Battery can be sharing
6. Up to 8 units in parallel
7. Manual maintenance bypass
8. Wide input voltage range
7. High output power factor
9. Strong environmental adaptability
10. Advanced battery management
11. N+X parallel redundancy
12. Compatible with generator
13. Strong shock resistance ability
14. EPO function
15. Full protection against over-discharge, overcharge, over load.
LBS function
· LBS function supports the two independent input to improve the reliability of the system.
High reliability
True on-line static bypass technology, to provide strong overload and fault protection device.
Internal manual maintenance bypass, further improve the reliability of continuous operation of the load.
Network management humanity
Communicate with PC by RS232.
Use SNMP adapter, UPS can realize remote network management function.
Optimized battery performance
Intelligent battery management function (ABM)
Automatically convert to constant-current constant-voltage charging technology.
Parallel Configuration of up to 8 units of Low Frequency Online UPS GP9332C 10-120KVA:
Can parallel 8 units UPS;
Parallel UPS units can share a battery pack;
Non-fixed master/slave parallel
Application:
large-medium computer data center, industrial process and other mission-critical equipment
Technical Specifications of Online UPS GP9332C 10-120KVA
Model |
GP9332C 10-120KVA |
|||||||||
Rated Power (KVA) |
10KVA |
15KVA |
20KVA |
30KVA |
40KVA |
60KVA |
80KVA |
100KVA |
120KVA |
|
Active Power (KW) |
8KW |
12KW |
16KW |
24KW |
32KW |
48KW |
64KW |
80KW |
90KW |
|
Input |
||||||||||
Nominal Voltage |
380/400/415VAC 3-phase |
|||||||||
Voltage tolerance |
400V + 20%/ -25% |
|||||||||
Frequency |
45 ÷ 65 Hz |
|||||||||
Soft Start |
0 ÷ 100% in 30’’ (selectable) |
|||||||||
Permitted frequency |
± 2% (selectable from ± 1% to ± 5% |
|||||||||
Standard features |
Back Feed protection; |
|||||||||
Battery |
||||||||||
Type |
Lead, flooded and VRLA AGM / GEL; NiCd |
|||||||||
AC ripple |
< 1% |
|||||||||
Temperature compensation |
-0.5V × ℃ |
|||||||||
Typical charging current |
0.2 × C10 |
|||||||||
Output |
||||||||||
Number of phase |
3 + N |
|||||||||
Nominal voltage |
380/400/415VAC 3-phase +N |
|||||||||
Static stability |
± 1% |
|||||||||
Dynamic stability |
± 5% in 10ms |
|||||||||
Voltage distortion |
<1% with linear load ; |
|||||||||
Crest factor |
3:1 |
|||||||||
Frequency stability on battery mode |
0.05% |
|||||||||
Frequency |
50 or 60Hz (selectable) |
|||||||||
Overload |
110% for 60’ ; 125% for 10’; 150% for 1’ |
|||||||||
Environment |
||||||||||
Remote signaling |
Voltage-free contacts |
|||||||||
Remote commands |
EPO and bypass |
|||||||||
Communication |
Double RS232 + remote contacts +2 |
|||||||||
Operating Temperature |
0 ℃ / + 40 ℃ |
|||||||||
Relative humidity |
< 95% non condensing |
|||||||||
Colour |
Light grey RAL 7035 |
|||||||||
Noise |
54 |
60 |
62 |
63 ÷ 68 |
||||||
Protection rating |
IP20 |
|||||||||
Efficiency Smart Mode |
Up to 98% |
|||||||||
Compliance |
European Directives: LV 2006/95/CE; |
|||||||||
Classification according |
(Voltage Frequency Independent) |
|||||||||
Physical parameters |
||||||||||
Weight (kg) |
210 |
220 |
230 |
280 |
330 |
450 |
600 |
640 |
650 |
|
Dimension |
1400 × |
1400 × |
1900 × |
Follow standard of GB/IEC regulation: EMC:GB7260.2/IEC62040-2 GB/17626.2~5/IEC61000-4-2~5 SAFETY:GB4943