Generator compatible three phase IGBT Low Frequency Online UPS 160KVA 400VAC
specifications
model |
CHP |
CHP |
CHP |
CHP |
CHP |
CHP |
CHP |
CHP |
CHP |
CHP |
CHP |
CHP |
CHP |
CHP |
|||
Nominal capacity (KVA) |
10 KVA |
20 KVA |
30 KVA |
40 KVA |
50 KVA |
60 KVA |
80 KVA |
100 KVA |
120 KVA |
160 KVA |
200 KVA |
250 KVA |
300 KVA |
400 KVA |
|||
Phase number |
3L+N+G |
||||||||||||||||
Input power factor |
≥0.85 (option ≥0.95) |
||||||||||||||||
rectifier |
Input rated voltage |
380VAC , 400VAC, 415VAC(option 208VAC, 220VAC) |
|||||||||||||||
range |
±25% |
||||||||||||||||
Input nominal frequency |
50Hz±10%, 60Hz±10% |
||||||||||||||||
Input overtone current |
6pulses rectifier<30% 12pulses rectifier plus filter <5% |
||||||||||||||||
Output ripple wave |
< 2% |
||||||||||||||||
Soft start |
0~100% 5sec |
||||||||||||||||
charging |
Charge mode |
Constant current first then constant voltage, charge with temperature compensation, automatic switch of even charge and float charge, programmable timing battery charge-discharge automatic maintenance |
|||||||||||||||
Float charging voltage |
432VDC |
||||||||||||||||
Equalized charging voltage |
445VDC |
||||||||||||||||
Temperature compensation voltage |
3mV/℃(cell battery) |
||||||||||||||||
Charging current |
0.1C(automatic adjust according to battery capacity) |
||||||||||||||||
Charging power |
20%of rated capacity |
||||||||||||||||
Battery |
type |
maintenance free lead-acid battery |
|||||||||||||||
capacity |
7~999AH settable (capacity vary with power) |
||||||||||||||||
battery number |
12V-32pcs, 2V-192pcs (nominal voltage 384VDC) |
||||||||||||||||
invertor |
Phase number |
3 phase+N |
|||||||||||||||
Rated power |
Rated capacity×0.9 |
||||||||||||||||
Nominal voltage |
380VAC , 400VAC, 415VAC(option 208VAC, 220VAC) |
||||||||||||||||
Output voltage stability |
±1%(steady load), ±3%(fluctuation of load) |
||||||||||||||||
Frequency stability |
50Hz, 60Hz<±0. 5%(desynchronised) |
||||||||||||||||
Factor of wave crest |
> 5:1 |
||||||||||||||||
Output Waveform distortion degree |
sine wave, linear load<3%; non-linear load<5% |
||||||||||||||||
Dynamic feature |
Transient voltage<±5%(jump form 0% to 100%), instant recovery time<10ms |
||||||||||||||||
Unbalance load voltage |
<±5% |
||||||||||||||||
Overload protection |
115% normal work 125% 10 min, 150%1min, 200%1s |
||||||||||||||||
Invertor efficiency |
>95%(full load) |
||||||||||||||||
bypass |
Phase number |
3 phase+N |
|||||||||||||||
Input nominal voltage |
380VAC , 400VAC, 415VAC(option 208VAC, 220VAC) |
||||||||||||||||
Output nominal voltage |
380VAC , 400VAC, 415VAC(option 208VAC, 220VAC) |
||||||||||||||||
Switching time |
0ms(adopted static switch ) |
||||||||||||||||
protection |
input protection |
voltage, frequency ultralimit, phase wrong, phase lost |
|||||||||||||||
Output protection |
overcurrent, short circuit, power factor low |
||||||||||||||||
Battery protection |
overcharge, overdischarge |
||||||||||||||||
Overheat protection |
Environmental thermal, inverter overheat protection |
||||||||||||||||
Hardware fault protection |
Auxiliary power supply abnormal, breaker trip, fuse break, power device overcurrent or overvoltage |
||||||||||||||||
System specifications |
Economic running mode |
Economic mode available, overall efficiency reach up to 98% |
|||||||||||||||
Audio alert function |
Any failure will be alerted |
||||||||||||||||
Work environment |
Ambient temperature: -30~50℃, relative humidity: 30%~90%, altitude: <2000M(power reduce 1% every 100M raised, 4000Mutmost) |
||||||||||||||||
Cooling method |
Forced ventilation |
||||||||||||||||
Telecom interface |
RS232, RS485. Dry contact interface, SNMP card(network remote control) |
||||||||||||||||
Redundancy function |
Cascade or multiple hot spare |
||||||||||||||||
Anti-surge |
10/700μS, 5KV;8/20μS, 20KA |
||||||||||||||||
Protection level |
IP31 |
||||||||||||||||
Safety performance |
I/O on ground resistance (3000VAC), stray current less than 3.5mA; insulation resistance exceeding 2MΩ(500VDC) |
||||||||||||||||
Noise(dB) |
48~55 |
55~60 |
60~65 |
65~70 |
|||||||||||||
Mechanical dimension (W×D×H)mm |
600×620×1200 |
600×720×1500 |
980×800×1800 |
1380×950×1800 |
1600×1150×1800 |
||||||||||||
Weight(Kg) |
200 |
265 |
310 |
342 |
385 |
402 |
560 |
850 |
910 |
1300 |
1680 |
1750 |
1830 |
1980 |
|||
CHP3000 series is three phase in and out online UPS, entirely surmounted the technical bottleneck in analog circuitry age, ingeniously applied the digital control technology and high-accuracy SMD technology which assured ultra-high system stability and is able to fully acclimate various grid environment, Single-machine capacity is ranging from 10KVA and 800KVA, widely used in telecom, bank, bond, traffic, utility, manufacture, etc.
Main features
Pure sine wave output, true online doubleconversion
7 inch colour LCD
Can be set to ECO mode
With EPO function
Can be with 100% unbalance load
Adopt the fourth layer PCB, and SMD technology
Sixth generation IGBT, much higher efficiency, lowetemperaturer, more reliable
Full protection, overload, over voltage, short circuit, over temperature etc
Cold start
Generator compatible
With RS232 and RS485 standard collocate,
Option SMMP and dry contact connection
Option battery manage function