Measurement of Dielectric Performance 
Measurement of Dielectric resistance
( 5000V scope 100000 MΩ meter oil temperature:21.6℃)
 
Measured part
Insulation resistance(MΩ)
Absorption rate 
Polarized index
R15
R60
R600
R60/R15
R600/R60
HV~LV and earth
49400
56900
84300
1.15
1.48
LV~HV and earth
33000
57800
97800
1.57
1.69
HV, LV~earth
19000
30000
50500
1.58
1.68
Upper clamp~core and earth
-
79700
-
-
-
Iron core~earth
-
37900
-
-
-
 end side of HV bushing~earth
-
4000
-
-
-
 
Measurement of Medium loss
Measured winding
Applied voltage kV
tgδ%
Cx(nF)
HV~LV and earth
10
0.17
10.08
LV~HV and earth
10
0.16
31.76
HV, LV~earth
10
0.15
33.30
HV bushing
10
0.36
0.493
 
 Measurement of voltage ratio and check of phase displacement
HV winding 
LV winding
Measure tolerance (%)
Phase displacement 
Tap 
Voltage (V)
Voltage (V)
 (1.1-1.2)/ (2.1-2.2)
A
317543
20000
+0.10
I, I0
B
309604
+0.04
C
301666
-0.03
 
 Measurement of winding resistance            oil temperature: 19℃
Winding 
Tap 
Measured value(Ω)
1.1-1.2
HV
A
0.3569
B
0.3483
C
0.3398
LV
2.1-2.2
0.0013121
 
 
 Measurement of no load loss and current 
Power supply terminal 
Applied voltage(kV)
No load current(%)
No load loss(kW)
Standard value
Measured value 
Standard value 
Measured value 
2.1-2.2
20
0.25+30%
0.11
103+15%
83.2
 
Measurement of loss and short circuit impedance  oil temperature: 21.6℃
Winding 
Measured item 
Tap 
Standard value
Measured value 
  HV power supply, LV short circuit  
Uk75℃(%)
A
13.35±7.5%
13.00
Pk75℃(kW)
445+15%
387.6
Uk75℃(%)
B
-
13.17
Pk75℃(kW)
-
398.2
Uk75℃(%)
C
-
13.21
Pk75℃(kW)
-
408.6
 
 Applied voltage withstand test 
Voltage applied part
Test voltage(kV)
Test time (s)
conclusion
HV(neutral)~LV and earth
140
60
Qualified 
LV~HV and earth
55
60
Qualified 
 
 Switching wave test  
Tap 
Voltage applied part
Earthed point 
Test voltage(kV)
Test wave
Conclusion 
A
1.1-1.2
1.2, 2.2
1175
Show in the following 
Passed 
Test Procedure:
One time negative switching wave impulse with 50% reduced voltage;
Three times negative switching wave impulse with 100% voltage;
There is no distortion between the wave of 50% voltage and 100% voltage. 
 
The wave and parameters are as following:
 
 
 
 
 
 
 
 
 
                  50%                                         100%
 
 
 
 
 
 
 
 
 
 
                  100%                                         100%
 
Lightening impulse test 
Tested items and conclusion 
Withstand terminal 
Rated withstand voltage(kV)
Tap 
Lightening, full wave
Lightening, chopped wave 
1.1
1425
-
A
Test Procedure:
One time negative switching wave impulse with 50% reduced voltage;
Three times negative switching wave impulse with 100% voltage;
There is no distortion between the wave of 50% voltage and 100% voltage.
 
 
 
 
The wave and parameters are as following:
 
 
 
 
 
                  50%                                         100%
 
 
                 100%                                         100%
 
Measurement of partial discharge        (ACLD power frequency  200 Hz)
Applied voltage, phase to earth(kV)
Measure time
Partial discharge(pc)
Measure when the oil pump stops 
-
HV
1.1Um
349.3
5min
50
1.5Um
476.3
5min
90
1.7Um
540
5s
-
1.5Um
476.3
0min
90
1.5Um
476.3
10min
90
1.5Um
476.3
20min
90
1.5Um
476.3
30min
90
1.5Um
476.3
60min
90
1.1Um
349.3
5min
50
Measurement of partial discharge when the oil pump starts(special)           (ACLD power frequency 200 Hz)
Applied voltage, phase to earth(kV)
Measure time
Partial discharge(pc)
Measure when the oil pump starts
-
HV
1.1Um
349.3
0-5min
50
1.5Um
476.3
0min
90
1.5Um
476.3
10min
90
1.5Um
476.3
20min
90
1.5Um
476.3
30min
90
1.5Um
476.3
60min
90
1.1Um
349.3
5min
50
 
 Test of Temperature rise
Test method 
Short-circuit 
tapping
C tap
Temperature rise of top oil(K)
47.5
Average temperature rise of HV winding(K)
55.7
Average temperature rise of LV winding(K)
60.3
Temperature rise of hot spot of enclosure(K)
46
 
 Long-time no loading of 12 hours  
Power supply terminal
Applied voltage(kV)
No load current(%)
No load loss(kW)
Test time 
2.1-2.2
22000
0.22
104500
12h
Test of transformer oil 
Oil No.:  45#
Sampling from the bottom of oil tank
Appearance:
Transparent, no suspended substance and foreign matters
flashover(closed)(℃):
142
Coefficient of medium loss(90℃)
0.002
Penetrating voltage(kV):
62
moisture(mg/kg)
8
 
Chromatogram of transformer oil 
Content (uL/L)
Items 
H2
CO
CO2
CH4
C2H6
C2H4
C2H2
Before test 
0.00
0.00
67.38
0.29
0.00
0.00
0.00
After impulse test(switching, lightening)
0.00
0.00
58.12
0.32
0.00
0.00
0.00
After partial test(before temperature rise)
0.00
0.00
64.45
0.18
0.00
0.00
0.00
After temperature rise(before long time no load)
0.00
0.00
69.00
0.21
0.00
0.00
0.00
After test of long time no loading
0.00
0.00
62.11
0.23
0.00
0.00
0.00
After oil flow test with electricity(partial discharge)
0.00
0.00
68.10
0.25
0.00
0.00
0.00
Gas content 
0.8 %
 
 Measurement of Harmonics of No load current(special)
 
Distortion of total harmonic 
--
U(kV)
U (%)
I(A)
I(%)
THD
2.400
12.0
9.187
110.5
Harmonic times 
--
U(kV)
U (%)
I(A)
I(%)
01
19.88
--
8.312
--
02
0.001
0.0
0.007
0.0
03
1.907
9.5
8.227
98.9
04
0.003
0.0
0.012
0.1
05
1.313
6.6
3.827
46.0
06
0.003
0.0
0.007
0.0
07
0.478
2.4
1.193
14.3
08
0.002
0.0
0.010
0.1
09
0.371
1.8
0.728
8.7
10
0.001
0.0
0.001
0.0
11
0.155
0.7
0.200
2.4
12
0.001
0.0
0.005
0.0
13
0.061
0.3
0.057
0.6
14
0.000
0.0
0.004
0.0
15
0.034
0.1
0.086
1.0
16
0.002
0.0
0.002
0.0
17
0.003
0.0
0.025
0.3
18
0.002
0.0
0.002
0.0
19
0.006
0.0
0.009
0.1
 
Measurement of sound level (special)
Standard value(sound power level)
Cooling device
A-weighted surface sound pressure level
A-weighted surface sound power level
101dB
stop(0.3 m)
76 dB
96 dB
start(2 m)
78.6 dB
99.3 dB
 
Measurement of the oil flow with electricity (special)
Test method: Start the oil pump for 4 hours, measure the leaking current of HV winding to earth, core to earth, which should be up to specified values.
Measure the partial no discharge signal without stopping the pump.
Pump starting time
HV winding to earth
Core to earth
Leaking current 
Leaking current
4 hours
<0.1uA
<0.1uA
Partial monitor 
No discharge signal 
No discharge signal
Measure the partial discharge at 1.5Um/√3 voltage without stopping the pumping, see the item 3.10, there is no change between the above measured value and that value measured without starting pump.