Product Main

Specifications

Multi Core PVC/PVC Cable Description or Construction

Multi Core PVC/PVC unarmored Cable

Voltage
0.6/1kV

Core Number
2-core, 3-core, 4-core, 5-core, 3+1 core, 3+2core, 4+1core

Conductor
Strand Copper or Aluminum

Insulation & sheath
PVC(Premature Ventricular Contraction)

Armored
non armour

Application
To be laid indoors, in tunnel, cable furrow or pipe, the cable couldn’t bear mechanical force outside

Executive standard
GB/T12706.1-2002(Equivalent IEC60502-1)Rated Voltage 1Kv (Um=1.2Kv) power cable

Working conditions
1) This maximum working temperature of the conductor is 70℃
2) During having a short(lasting less than 5 seconds)the maximum temperature of the cable conductor for shall not be above 160℃
3) Environment temperature should be no lower than 0℃ for laying the cable
4) Bending radius allowance of the cable;
single core cable: no steel tape cable 20D: steel tape cable 15D.
3 core cable: no steel tape cable 15D; steel tape cable 12D.

 

multi core pvc/pvc unarmored cable
Nom.Cross
sec.Area of
conductor
Single
quantity of
Conductor
thickness Sheath
thickness
Approx.Dia
of cable
Cable
approx.Weight
D.C.Resisance Test
voltage
(ac)
Cu Al 20℃Cu 20℃Al
Mm² mm mm mm Kg/km Kg/km

Ω/km

Ω/km

Kv/5min
2x1.5 1 0.8 1.8 10.4 119 100 12.1 / 3.5
2x2.5 1 0.8 1.8 11.1 150 118 7.41 12.1 3.5
2x4 1 1.0 1.8 12.8 210 160 4.61 7.41 3.5
2x6 1 1.0 1.8 13.8 264 192 3.08 4.61 3.5
2x10 7 1.0 1.8 16.4 393 242 1.83 3.02 3.5
2x16 7 1.0 1.8 18.5 541 334 1.15 1.91 3.5
2x25 7 1.2 1.8 21.9 794 469 0.727 1.20 3.5