Flexible insulated busbars consist of several layers of uncoated or tinned copper strips and are insulated with flexible high quality PVC compound.
 
 
 
 
Technical data of electrical conductor
   Copper strips (≥99.9%Cu).
   Surface: uncoated or tinned.
   Resistivity: ≤1.785μΩcm2/cm.
   Electrical conductivity: ≥55 Sm/mm2.
   Tensile strength: ≥200N/mm2.
   Extensibility: ≥30%.
 
Technical data of insulation
   Material: PVC.
   Color: black.
   Thickness: 1.8-2.1mm.
   Shore hardness: A70-80.
   Electrical strength: ≥23kV/mm.
   Oxygen index: 30%.
   Flame retardant; self-extinguishing.
   Elasticity: ≥180% after 7-day aging-test with 135℃.
   Tensile strength: ≥20MPa.
 
Technical data of flexible insulated busbars
   Operating temperature: -30℃ to +105℃.
   Operating voltage: 750V.
   Voltage withstand performance with 15min / 50Hz AC:
      - between flexible insulated busbar and earth: ≥15kV.
      - between two flexible insulated busbars: ≥30kV.
 
Main features of flexible insulated busbars
   Easy assembly: it could be easily bended and fixed with hands or easy tools.
   Possibility of reducing sizes of the equipment:
      - Due to favorable thermal radiation properties, the flexible insulated busbars can handle
        heavier current loads than solid busbars of the same cross-section.
      - Due to good insulating performance of the PVC, it could be possible to reduce the
        distances between different flexible insulated busbars and between the flexible insulated 
        busbars and earth.
      - The bending-radius could be smaller than that of normal cable or solid copper bars, so
        that the connections could be more simple and short, and visually it could have better effect.
   Lower temperature rise on the flexible insulated busbars than on normal copper bars.
   High flexibility: no problem with vibrations or thermal expansions.
 
 
 
Application of flexible insulated busbars
The flexibility of the bars makes it possible to install them into difficult equipment or small places very easily. They will be particularly well used as connectors in switchgears and between transformers, switching devices and prefabricated power networks.
 
Dimensions and ampacity
   Standard conductor: copper (99.9%), uncoated or tinned.
   Standard length: 2m (for 1-layer busbar, 25m is possible).
   Cross-section: up to 1200mmm2.
   Color of insulation: black.
   Ampacity: values are only for information because the actual ampacity is related to the
      application conditions.
 
 
 
Dimensions and
Qty. of strips
 
Cross section (mm2)
 
Ampacity (A)
Dimensions and
Qty. of strips
Cross section (mm2)
Ampacity (A)
△T=20K  (3)
△T=40K  (4)
 
△T=50K  (5)
△T=20K  (3)
△T=40K  (4)
△T=50K  (5)
15.5*0.8*2
24.8
125
175
200
40*1*2
80
240
330
380
15.5*0.8*3
37.2
160
210
240
40*1*3
120
330
480
540
15.5*0.8*4
49.6
195
265
295
40*1*4
160
400
560
630
15.5*0.8*6
74.4
225
320
360
40*1*5
200
450
630
710
15.5*0.8*8
99.2
265
380
430
40*1*6
240
480
680
750
15.5*0.8*10
124
300
420
480
40*1*8
320
600
830
920
20*1*2
40
170
240
270
40*1*10
400
670
920
1030
20*1*3
60
230
320
360
50*1*3
150
400
570
650
20*1*4
80
270
380
440
50*1*4
200
490
700
790
20*1*5
100
300
430
490
50*1*5
250
540
780
880
20*1*6
120
330
470
530
50*1*6
300
590
840
950
20*1*8
160
400
560
620
50*1*8
400
680
1000
1130
20*1*10
200
420
580
650
50*1*10
500
750
1100
1300
24*1*2
48
200
280
320
63*1*5
315
650
900
1000
24*1*3
72
250
360
410
63*1*6
378
690
980
1100
24*1*4
96
280
410
460
63*1*8
504
840
1200
1350
24*1*5
120
330
470
530
63*1*10
630
920
1300
1450
24*1*6
144
360
510
570
80*1*5
400
700
1100
1230
24*1*8
192
420
590
670
80*1*6
480
780
1210
1360
24*1*10
240
500
700
790
80*1*8
640
950
1400
1570
32*1*2
64
230
320
360
80*1*10
800
1090
1550
1730
32*1*3
96
280
410
460
100*1*5
500
860
1250
1400
32*1*4
128
320
460
520
100*1*6
600
950
1380
1530
32*1*5
160
390
550
610
100*1*8
800
1100
1580
1760
32*1*6
192
440
620
700
100*1*10
1000
1220
1710
1920
32*1*8
256
510
720
822
100*1*12
1200
1300
1800
2010
32*1*10
320
600
840
930