Product Main

Specifications

UPS Power - Santak UPS Power 1K-20Kva With LCD Display and 0.8 Power Factor

High Frequency Online UPS Tomorrow Star Series
TS6K-10KVA (1Ph in/1Ph out); 31TS10K-20KVA (3Ph in/1Ph out)
 
Key Features
●Tailored for Grid Environment
●Flexible Configuration on Demand
●Compact Design, Lower Noise
●Intelligent battery management
●Rich Communication and Monitoring Features
●High Reliability
 
 
Tomorrow Star Series 6K-20Kva
Standard Model (S)
TS6K
TS10K
31TS10K
-
-
 
Long Run Model (L)
TS6KL
TS10KL
31TS10KL
31TS15L
31TS20KL
 
Capacity
6Kva/4.8Kw
10Kva/8Kw
10Kva/8Kw
15Kva/12Kw
20Kva/16Kw
 
Phase
1/1PHASE, 1wire+N+G
3/1APHASE, 3Wires+N+G
 
Input  PF
Above0.99
 
THDI
Less than 6%
 
Input voltage
Low transfer
L-N:176 VAC ± 3% @ 100% load;130 VAC ± 3% @ 50% load
 
Low back
L-N:188 VAC ± 3% @ 100% load, 142 VAC ± 3% @ 50% load
 
High transfer
L-N:286 VAC ± 3%
 
High back
L-N:270 VAC ± 3%
 
Input frequency
40-70hz
 
Battery
 
DC voltage
192Vdc/240Vdc(INBUILT/EXTERNAL)                  
192Vdc/240Vdc (EXTERNAL)
 
Charge voltage
220Vdc/275Vdc
 
Recharging current
4A(L)/1A(S)
4/8A
 
Battery type
Lead-acid Maintenance-free battery
 
Battery quantity
16/20PCS*12VDC
 
Output
 
Output PF
0.8
 
Output voltage
220/230/240Vac +/-1%(static)
 
Frequency
46~54Hz or 56~64Hz (Line mode), 50/60Hz ± 0.1Hz ( Battery mode)
 
crest factor
3:1(max)
 
Wave distortion
Less than 2%(linear load), Less than 4% Non-linear load
 
Over load
105%<load<125% for 1 mins , 125%<load<150% for30sec
 
Transfer time
0ms (AC-Battery); 0 ms(bypass-inverter)
 
Parallel
6PCS(Max.)
 
Indicator
 
LCD Panel
UPS status, Load level, Load watt, Load VA, Battery level, Input/Output voltage, output current, Bus voltage, Temp, and warning and fault code and events
 
Alarm
 
Battery Mode
Sounding every 4 seconds( can mute)
 
Low Battery
Sounding every second
 
Overload
Sounding every second
 
Fault
Continuously sounding
 
Management
 
Smart RS-232/USB
Supports Windows® 2000/2003/XP/Vista/2008,                             Windows® 7, Linux, Unix, and MAC
 
Optional
SNMP/AS400
 
Environment
 
Operation Humidity
0-90 % RH (non-condensing) @ 0- 40°C
 
Noise Level
Less than 55dBA @ 1 Meter
Less than 58dBA @ 1 Meter
 
Physical
 
Net Weight (KG)
28(L)/65(S)
29(L)/66(S)
36(L)/66(S)
48
48
 
Gross Weight(KG)
40(L)/77(S)
41(L)/78(S)
48(L)/78(S)
57
57
 
Dimension/MM (L*H*D)
260*642*582 / 370*792 *682(Unit/Packing)
290*642*600/
390*810*700
(Unit/Packing)
300*600*742/ 420*920*720
(Unit/Packing)
 
 
 
*Speciifcation are subject to change without prior notice