Product Description
Application:
CC1-D series AC contactor is suitable for suing in the circuits up to rated voltage 660V AC 50/60Hz, rated current up to 95A, for making, breaking, frequently starting & controlling the AC motor. Combined with the auxiliary contactor, mechanical interlocking contactor, and star-delta starter. With the thermal relay, it is combined into the electromagnetic starter.
The contactor is produced according to IEC60947-4, VDE0660 & BS5452.
The product is CB and SEMKO certified by INTERTEK.
Specification:
CC1-D09, CC1-D12, CC1-D18
CC1-D25, CC1-D32, CC1-D40
CC1-D50, CC1-D65, CC1-D80
CC1-D95, CC1-D115, CC1-D150
CC1-D170, CC1-D205, CC1-D245
CC1-D300, CC1-D410, CC1-D475
CC1-D620
Number of the Contact: 3P+NO, 3P+NC
Standard control circuit Voltage:
24V(B7), 42V(D7), 48V(E7), 110V(F7), 220/230V(M7), 230V(P7), 240V(U7), 380/400V(Q7), 400V(V7), 415V(N7).
CC1-D series AC contactor is suitable for suing in the circuits up to rated voltage 660V AC 50/60Hz, rated current up to 95A, for making, breaking, frequently starting & controlling the AC motor. Combined with the auxiliary contactor, mechanical interlocking contactor, and star-delta starter. With the thermal relay, it is combined into the electromagnetic starter.
The contactor is produced according to IEC60947-4, VDE0660 & BS5452.
The product is CB and SEMKO certified by INTERTEK.
Specification:
CC1-D09, CC1-D12, CC1-D18
CC1-D25, CC1-D32, CC1-D40
CC1-D50, CC1-D65, CC1-D80
CC1-D95, CC1-D115, CC1-D150
CC1-D170, CC1-D205, CC1-D245
CC1-D300, CC1-D410, CC1-D475
CC1-D620
Number of the Contact: 3P+NO, 3P+NC
Standard control circuit Voltage:
24V(B7), 42V(D7), 48V(E7), 110V(F7), 220/230V(M7), 230V(P7), 240V(U7), 380/400V(Q7), 400V(V7), 415V(N7).
Volts(VAC) | 24 | 42 | 48 | 110 | 220 | 230 | 240 | 380 | 400 | 415 | 440 | 500 | 600 |
50Hz | B5 | D5 | E5 | F5 | M5 | P5 | U5 | Q5 | V5 | N5 | R5 | S5 | Y5 |
60Hz | B6 | D6 | E6 | F6 | M6 | - | U6 | Q6 | - | - | R6 | - | - |
50/60Hz | B7 | D7 | E7 | F7 | M7 | P7 | U7 | Q7 | V7 | N7 | R7 | - | - |
Type | CC1-D09 | CC1-D12 | CC1-D18 | CC1-D25 | CC1-D32 | |
Rated operation current (A) |
AC-3 | 9 | 12 | 18 | 25 | 32 |
AC-1 | 3.5 | 5 | 7.7 | 8.5 | 12 | |
Standard power rating of 3-phase motors AC-3(KW) |
220/230V | 2.2 | 3 | 4 | 5.5 | 7.5 |
380/400V | 4 | 5.5 | 7.5 | 11 | 15 | |
415V | 4 | 5.5 | 9 | 11 | 15 | |
440V | 4 | 5.5 | 9 | 11 | 15 | |
500V | 5.5 | 7.5 | 10 | 15 | 18.5 | |
660/690V | 5.5 | 7.5 | 10 | 15 | 18.5 | |
Rated heat current (A) Ith | 20 | 20 | 32 | 40 | 50 | |
Electrical life |
AC4x10000 | 20 | 20-15 | 20-7 | 15-7 | 15-7 |
AC3x1000000 | 2 | 2 | 2 | 2 | 2 | |
Mechanical life x 1000000 | 20 | 20 | 20 | 20 | 20 | |
Number of contact |
3P+NO | |||||
3P+NC |
Type | CC1-D40 | CC1-D50 | CC1-D65 | CC1-D80 | CC1-D95 | |
Rated operation current (A) |
AC-3 | 40 | 50 | 65 | 80 | 95 |
AC-1 | 18.5 | 24 | 28 | 37 | 44 | |
Standard power rating of 3-phase motors AC-3(KW) |
220/230V | 11 | 15 | 18.5 | 22 | 25 |
380/400V | 18.5 | 22 | 30 | 37 | 45 | |
415V | 22 | 25 | 37 | 45 | 45 | |
440V | 22 | 30 | 37 | 45 | 45 | |
500V | 22 | 30 | 37 | 55 | 55 | |
660/690V | 30 | 33 | 37 | 45 | 45 | |
Rated heat current (A) Ith | 60 | 80 | 80 | 125 | 125 | |
Electrical life |
AC4x10000 | 10-7 | 7 | 7-6 | 7-5 | 7-5 |
AC3x1000000 | 2 | 2 | 1.6 | 1.6 | 1.6 | |
Mechanical life x 1000000 | 20 | 20 | 20 | 10 | 10 | |
Number of the contact | 3P+NO+NC |