CAW1 Air Circuit Breaker
Air circuit breaker is suitable for the circuit of AC 50Hz with rated voltage up to 690V and rated current up to 6300A. It is mainly used to distribute electric energy and protect circuit and power supply equipment from overload, under voltage, short circuit and single phase earthing with intelligentized and selective protection function, the breaker can improve the reliability of power supply and avoid unnecessary power failure. The breaker is applicable for power stations, factories, mines (for 690V) and modern high-buildings, especially for the distribution system of intelligentized building.
Application:
. Rated operational voltage of the breaker is AC400/415/690V, with the rated current ranges from 400A to 6300A
. Compact design with fixed and withdrawerable type
. Standar: IEC/EC 60947-2
. Telecommunication protocal: The protocals of Modbus, Profibus-DP and Device Net are avaiable
. Breaking capacity under 415V
Model:
CAW1-2000 400A, 630A, 800A, 1000A, 1250A, 1600A, 2000A
CAW1-3200 2000A, 2500A, 2900A, 3200A
CAW1-4000 3200A, 3900A, 4000A
CAW1-6300 4000A, 5000A, 6000A, 6300A
Air circuit breaker is suitable for the circuit of AC 50Hz with rated voltage up to 690V and rated current up to 6300A. It is mainly used to distribute electric energy and protect circuit and power supply equipment from overload, under voltage, short circuit and single phase earthing with intelligentized and selective protection function, the breaker can improve the reliability of power supply and avoid unnecessary power failure. The breaker is applicable for power stations, factories, mines (for 690V) and modern high-buildings, especially for the distribution system of intelligentized building.
Application:
. Rated operational voltage of the breaker is AC400/415/690V, with the rated current ranges from 400A to 6300A
. Compact design with fixed and withdrawerable type
. Standar: IEC/EC 60947-2
. Telecommunication protocal: The protocals of Modbus, Profibus-DP and Device Net are avaiable
. Breaking capacity under 415V
Model:
CAW1-2000 400A, 630A, 800A, 1000A, 1250A, 1600A, 2000A
CAW1-3200 2000A, 2500A, 2900A, 3200A
CAW1-4000 3200A, 3900A, 4000A
CAW1-6300 4000A, 5000A, 6000A, 6300A
Model | CAW1-2000 | CAW1-3200 | CAW1-4000 | CAW1-6300 | |
Frame size rated current In(A) | 2000 | 3200 | 4000 | 6300 | |
Number of poles | 3.4 | 3,4 | 3,4 | 3,4 | |
Rated current In(A) | (400),630,800,1000,1250,1600,2000 | 2000,2500,3200 | 4000 | 4000,5000,6300 | |
Icu(kA) | 400/415V | 80 | 80(100) | 80(100) | 120 |
690V | 50 | 65 | 65 | 80 | |
Ics=Icw(kA) | 400/415V | 50 | 65 | 65 | 100 |
690 | 40 | 50 | 50 | 65 | |
Rated current at N-pole In(A) | 50%In, 100%In | 50%In,100%In | 50%In | 50%In | |
Inherent making & breaking time | 23-32ms | 23-32ms | 23-32ms | 23-32ms | |
Operating performances (operations) |
Electric life (under AC415V) | 500(1000) | 500(1000) | 500(1000) | 500 |
Mechanical life |
Maintenance-free 2500 Maintainable 1000 |
Maintenance-free 2500 Maintainable 1000 |
Maintenance-free 2500 Maintainable 1000 |
||
Mounting mode | Fixed. Withdrawable | Fixed. Withdrawable | Withdrawable | ||
Arcing distance (mm) | 0 | 0 | 0 | ||
Intelligent controller |
Standard type (M) | -- | -- | -- | |
Telecommunication type (H) | -- | -- |