BT P C 255 RM
Product Description:
For installation at LPZ 0B-1 or higher, prevent low voltage devices from surge damages.
Applied in Class Ⅱ(Class C) power supply system, according to GB 18802.1-2002 / IEC 61643-1:1998-02.
Main character:
※ Especially for “3+1” lines in TT system, installed between the line (N) and (PE)
※ Standard single chip structure, high discharge capacity, pluggable
※ Quick response
※ Multifunctional terminals for connection of conductors and Bus Bar
※ Green window will change when fault occurs, also provide remote alarm terminal at the same time
Parameters:
Type
|
|
BT P C 255 RM
|
||
Order No.
|
|
810 100
|
||
Rated voltage
(max. Continuous voltage)
|
Uc
|
255V~
|
||
Nominal discharge
current (8/20)
|
In
|
40KA
|
||
Max. discharge
current (8/20)
|
Imax
|
60KA
|
||
Voltage protection
level at In
|
Up
|
≤ 1.5KV
|
||
Follow current extinguishing
capability at Uc
|
If
|
100rms
|
||
Response time
|
tA
|
≤ 100ns
|
||
Operating temperature range
|
θ
|
-40℃…+80℃
|
||
Max. backup fuse
|
|
125A gL / gG
|
||
Cross-section area
|
|
1.5mm2~25mm2 solid/35mm2 flexible
|
||
Mounting on
|
|
35mm DIN rail
|
||
Enclosure material
|
|
Purple thermoplastic, UL94-V0
|
||
Dimension
|
|
1 mods
|
||
Test standards
|
|
YD/T 1235.1-2002; GB 18802.1-2002; IEC 61643-1:1998-02
|
||
Certification
|
|
CE (LVD, EMC)
|
||
BT P C 255 RM Additional information
|
||||
Type of remote
signalling contact
|
|
Switching contact
|
||
Switching capacity
|
UN/IN
|
AC: 250V/0.5A; DC: 250V/0.1A, 125V/0.2A, 75V/0.5A
|
||
Cross-sectional area for
remote signalling contact
|
|
Max. 1.5mm2 solid/flexible
|