Product Main

Specifications

BT P C 255 RM
 
Product Description:
For installation at LPZ 0B-1 or higher,  prevent low voltage devices from surge damages.
Applied in Class Ⅱ(Class C) power supply system, according to GB 18802.1-2002 / IEC 61643-1:1998-02.
 
Main character:
※     Especially for “3+1” lines in TT system, installed between the line (N) and (PE)
※     Standard single chip structure, high discharge capacity, pluggable
※     Quick response
※     Multifunctional terminals for connection of conductors and Bus Bar
※     Green window will change when fault occurs, also provide remote alarm terminal at the same time
 
 
Parameters:
 
 
Type
 
BT P C 255 RM
Order No.
 
810 100
Rated voltage
(max. Continuous voltage)
Uc
255V~
Nominal discharge
current (8/20)
In
40KA
Max. discharge
current (8/20)
Imax
60KA
Voltage protection
level at In
Up
≤ 1.5KV
Follow current extinguishing
capability at Uc
If
100rms
Response time
tA
≤ 100ns
Operating temperature range
θ
-40℃…+80℃
Max. backup fuse
 
125A gL / gG
Cross-section area
 
1.5mm2~25mm2 solid/35mm2 flexible
Mounting on
 
35mm DIN rail
Enclosure material
 
Purple thermoplastic, UL94-V0
Dimension
 
1 mods
Test standards
 
YD/T 1235.1-2002; GB 18802.1-2002; IEC 61643-1:1998-02
Certification
 
CE (LVD, EMC)
BT P C 255 RM Additional information
Type of remote
signalling contact
 
Switching contact
Switching capacity
UN/IN
AC: 250V/0.5A;  DC: 250V/0.1A, 125V/0.2A, 75V/0.5A
Cross-sectional area for
remote signalling contact
 
Max. 1.5mm  solid/flexible