BT P60 TT ... RM
Product Description:
For installation at LPZ 0B-1 or higher, protecting low voltage equipment from surge. Specially designed for TT and TN-S system (“3+1”circuit). Designed according to GB 18802.1-2002/IEC 61643-1:1998-02.
Main character:
※ Small volume, high discharge capacity, pluggable
※ Quick response
※ Double thermal disconnection device , provide more reliable protection
※ Multifunctional terminals for connection of conductors and Bus Bar
※ Green window will change when fault occurs, also provide remote alarm terminal at the same time
Parameters:
|
Type
|
|
BT P60 TT 275 RM
|
BT P60 TT 385 RM
|
|
Order No.
|
|
810 133
|
810 135
|
|
Rated voltage L-N
(max. Continuous voltage)N-PE
|
Uc
|
275V~
255V~
|
385V~
255V~
|
|
Nominal discharge L-N
current (8/20) N-PE
|
In
|
20KA
40KA
|
20KA
40KA
|
|
Max. discharge L-N
current (8/20) N-PE
|
Imax
|
60KA
60KA
|
60KA
60KA
|
|
Voltage protection
level at 5kA (8/20) L-N
|
Up
|
≤1000V
|
≤1350V
|
|
Voltage protection L-N
level at In N-PE
|
Up
|
≤1250V
≤1500V
|
≤1800V
≤1500V
|
|
Response time L-N
N-PE
|
tA
|
≤ 25ns
≤ 100ns
|
≤ 25ns
≤ 100ns
|
|
Max. backup fuse
|
|
125A gL/ Gg
|
|
|
Operating temperature range
|
θ
|
-40℃…+80℃
|
|
|
Follow current extinguishing
capability at Uc
|
|
100Arms
|
|
|
Cross-section area
|
|
1.5mm2~25mm2 solid/35mm2 flexible
|
|
|
Mounting on
|
|
35mm DIN rail
|
|
|
Enclosure material
|
|
Purple thermoplastic, UL94-V0
|
|
|
Dimension
|
|
4 mods
|
|
|
Test standards
|
|
YD/T 1235.1-2002; GB 18802.1-2002; IEC 61643-1:1998-02
|
|
|
Certification
|
|
CE (LVD, EMC)
|
|
|
BT P60 TT… RM Additional information
|
|||
|
Type of remote
signalling contact
|
|
Switching contact
|
|
|
Switching capacity
|
UN/IN
|
AC: 250V/0.5A; DC: 250V/0.1A, 125V/0.2A, 75V/0.5A
|
|
|
Cross-sectional area for
remote signalling contact
|
|
Max. 1.5mm2 solid/flexible
|
|