Product Main

Specifications

Copper conductor XLPE insulated aerial cable
 
Standard
The product applies for transmitting line and distributing line of rated voltage 1KV, 10KV and 35KV in tall buildings, travelling development and wooded tract.
 
Characteristics
1. The rated voltage has three classes: 0.6/1KV ,10KV and 35KV.
2. Continuous permissible operating temperature
       PVC insulation: 70°C
       PE insulation: 70°C
       HDPE insulation: 75°C
   XLPE insulation: 90°C
3. Max. Temperature of cable under short circuit (5 sec. max duration).
       PVC insulation: 160°C
       PE insulation: 130°C
       HDPE insulation: 150°C
   XLPE insulation: 250°C
4. Laying temperature should be not less than -40°C.
5. Operating environmental temperature scope is -40~40°C.
6. Permissible bending radius of cable
       ( D for overall diameter of cable, d for overall diameter of conductor)
 
Rated voltage
The bending radius
D < 25
D ≥ 25
0.6/1KV
 4 times more than D
6 times more than D
 
Rated voltage
The bending radius
Single core
Multi-core 
10KV
35KV
more than 20(D+d)
more than 15(D+d)
 
 
Prodution scope
Type
Rated voltage
Number of cores 
Nominal cross area(mm2)
JKV,JKLV,JKY,JKLY,JKYJ,JKLYJ,
JKLHYJ,JKLHV,JKLGY,JKLGYJ
0.6/1kV
1
16 ~ 240
2
4
10 ~120
JKLV,JKLY,JKLYJ
3+K
10 ~120
JKYJ,JKTRYJ,JKLYJ,JKLHYJ,JKY,JKTRY,JKLY,
JKLHY,JKLYJ/Q,JKLHYJ/Q,JKLY/Q,JKLHY/Q,JKLGY,JKLGYJ
10kV
1
10 ~ 300
JKYJ,JKTRYJ,JKLYJ,JKLHYJ,JKLYJ/B,JKLHYJ/B
3
25 ~ 300
JKYJ,JKLYJ,JKTRYJ,JKLHYJ,JKLYJ/B,JKLHYJ/B
3+K(A)3+K(B)
25 ~ 300
K25~120
JKYJ,JKTRYJ,JKLYJ,JKLHYJ,JKLGYJ
35kV
1
50 ~ 300