Inverter Model
|
EPVF 4000W
|
EPVF 5000W
|
EPVF 6000W
|
DC OUTPUT DATA
|
|||
Continuous Output Power
|
4000W
|
5000W
|
6000W
|
Surge Rating
|
8000W
|
10000W
|
12000W
|
Output Waveform
|
Pure Sine wave/Same as input(Bypass mode)
|
||
Nominal Efficiency
|
>88%(Peak)
|
||
Line Mode Efficiency
|
>95%
|
||
Power Factor
|
0.9-1.0
|
||
Nominal Output Voltage rms
|
120/230VAC
|
||
Output Voltage Regulation
|
±10% rms
|
||
Output Frequency
|
50Hz ± 0.3Hz/60Hz ± 0.3Hz
|
||
Short Circuit Protection
|
Yes( 10s after fault )
|
||
Typical Line Stansfer Time
|
8ms
|
||
THD
|
<3%
|
||
AC INPUT DATA
|
|||
Nominal Input Voltage
|
24V
|
48V
|
|
Minimum Start Voltage
|
20V
|
40V
|
|
Low Battery Alarm
|
21V
|
42V
|
|
Low Battery Trip
|
20V
|
40V
|
|
High Voltage Alarm
|
32V
|
64V
|
|
Idle Consumption-Search Mode
|
< 25 W when Power Saver On
|
||
CHARGE
|
|||
Input Voltage Range
|
194-243VAC
|
164-243VAC(W)
|
|
Output Voltage
|
Depends on battery type
|
||
Max Charge Rate
|
35A / 70A
|
||
Battery Initial Voltage for Start Up
|
0-15.7V for 12V( *2 for 24V, *4 for 48V)
|
||
Over Charge Protection Shutdown
|
15.7V for 12V (*2 for 24V, *4 for 48V)
|
||
Charger curve(4 stage constant current)Battery types 4 step digital controlled progressive charge
|
|||
Battery type
|
Fast V Float V ( *2 for 24v, *4 for 48v)
|
||
Gel U.S.A
|
13.7
|
||
A.G.M 1
|
13.4
|
||
A.G.M 2
|
13.7
|
||
Sealed Lead Acid
|
13.6
|
||
Gel Euro
|
13.8
|
||
Open Lead Acid
|
13.3
|
||
Calcium
|
13.6
|
||
De-sulphation
|
15.5 for 4hrs
|
||
Remote Control
|
Yes. Optional
|
||
BYPASS & PROTECTION
|
|||
Input Voltage Waveform
|
Sine wave (Grid or Generator)
|
||
Nominal Voltage
|
230VAC
|
||
Low Voltage Trip
|
184V/154V±4%
|
||
Low Voltage re engage
|
194V/164V±4%
|
||
High Voltage Trip
|
253V±4%
|
||
High Voltage re engage
|
243V±4%
|
||
Max Input AC Voltage
|
270VAC
|
||
Nominal Input Frequency
|
50Hz or 60Hz (Auto detect)
|
||
Low freq trip
|
47Hz for 50Hz, 57Hz for 60Hz
|
||
High freq trip
|
55Hz for 50Hz, 65Hz for 60Hz
|
||
Overload protection
|
Circuit breaker
|
||
Short circuit protection
|
Circuit breaker
|
||
Transfer switch rating
|
40amp
|
||
Bypass without battery connected
|
Yes
|
||
Max bypass current
|
40amp
|
||
Bypass over load current
|
45amp: Alarm
|
||
MECHANICAL SPECIFICATIONS
|
|||
Mounting
|
Wall mount
|
||
Inverter Dimensions(L*W*H)
|
598*218*179mm
|
||
Inverter Weight
|
35KG
|
45KG
|
45KG
|
Shipping Dimensions(L*W*H)
|
740*315*300mm
|
||
Shipping Weight
|
37KG
|
47KG
|
47KG
|
Display
|
Status LEDs / Status LEDs+LCD
|
||
Standard Warranty
|
1 Year
|