3*2.5mm2, 6mm2, 10mm2 0.6/1kV XLPE/SWA/PVC Power Cable
 
 
Standard
 
The product is manufactured according to the standard of IEC6052, GB12706 or IEC,BS,DIN and ICEA upon request
 
 
 
Applications
 
The product  is suitable for use in power transmission and distribution lines with rated power frequency voltage 0.6/kV-26/35kV
 
 
 
Conductor: Solid or stranded Copper/Aluminum
 
-Insulation: Cross-linked polyethylene( XLPE or PVC)
-Circuit Indentation: The insulation shall be red, black
-Filler: Polypropylene lament with lapped binding tape
-Inner Sheath: Polyvinyl chloride (Black)
-Armor: Galvanized steel wire/steel tape/Unarmored/Aluminum wire
-Core-covering: Binding tape
-Outer Sheath: Polyvinyl chloride (Black)
 
 
 
Operating characteristics
 
1. Rated power-frequency voltage Uo/U: 3.6/kV-26/35kV
 
2. Max.permissible continuous operating temperature of conductor: 90°C
 
3. Max.short-circuit temperature of conductor shall not exceed 250(5s maximum duration )
 
4. The ambient temperature under installation should not below 0°C
 
5. The bending radius of a single-core power cable should not less than 20 times of the cable diameter. The bending radius of a three-core power cable should not less than 15 times of the cable diameter.