Brand Name: ZOANCO
Sensor: photoelectric
Size: 103x55mm
ITEM: conventional photoelectric smoke detector
power: 9 to 28 VDC Volts Non-polarized
Model Number: yt102
Place of Origin: China (Mainland)
Operating Voltage Range: 9 to 28VDC Volts Non-polarized
Standby Current: <60uA @ 24 VDC
Maximum Alarm Current (LED on: ): <30mA @ 24 VDC
Adjustable Sensitivity: 0.15-0.3dB/m
size: 103x55mm
weight: 155g

Specifications


Skype firealarm87  /wechat 15220176087

the device is photoelectronic detector uses a state of-the-art Optical sensing chamber. this detector is designed to provide open area Protection and to be used with most conventional fire alarm control panel.

Two LEDs on each detector Provide local 360 visible alarm indication. They flash every 3~5 seconds Indicating that power is applied and the detector is working properly. The LEDs Latch on in alarm. LEDs will be off when a trouble condition exists indicating that the detector sensitivity is outside the listed limit. The alarm can be Reset only by a momentary power interruption. 

Technical specifications

OperatingVoltageRange:             9 to 28VDC Volts Non-polarized

Standby Current:                  60A @ 24 VDC

Maximum Alarm Current (LED on: )30mA @ 24 VDC

OperatingHumidityRange:          10% to 93% Relative Humidity, Non-condensing

OperatingTemperatureRange:        14Fto122F(-10Cto50C)

Adjustable Sensitivity:             0.150.3dB/m

Height:                           2.2 (55 mm) installed in Base

Diameter:                              4.0 (103 mm)

Weight:                         5.5 oz. (155 g)


INSTALLATION

NOTE: All wiring must conform to applicable local codes, ordinances, and Regulations.

NOTE: Verify that all detector bases are installed, that the Initiating-device circuits have been tested, and that the wiring is correct.

 

Remove power from Initiating-device circuits before installing detectors.

 

1. Wire the sensor base per the wiring diagram, Figure 1.

2. Install the sensor into the sensor base. Push the sensor into the Base while turning it clockwise to secure it in place.

3. after all sensors have been installed, apply power to the control Unit.

4. Test the sensor(s) as described in the TESTING section

of this manual.

5. Notify the proper authorities that the system is in operation.