1.Application
GSG1-100 range separated switch (shortened form separated switch) mainly use in the electricity-distribution networks as the master switch of the power supply to break or make the circuits with loads. When it in switching-on status, it can take the normal working current as well as the specified faulty current within the specified time to ensure the power continuousness of the networks and circuits;while it is in the switching-off status, it can provide the reliable insulating gap to make the electricity-consumer equipment as well as the circuit to be isolated with the power supply and to prevent the electricity-consumer equipments from being damaged due to the over voltage and also ensure the safety maintenance working for the electricity-consumer equipment.
2.Structure feature
Products accord with the IEC60947.3, GB14048.3 substances
Through the CCC certification, the EU CE safety certification.
3.Main technical parameters
item
|
parameters
|
note
|
type
|
GSG1-100
|
|
Usage classification
|
AC-22
|
|
Rated Insulation voltage
|
415V
|
|
Rated operating voltage
|
240/415V
|
|
Frequency
|
50/60HZ
|
|
Convention thermal current
|
100A
|
|
Rated operating current
|
32A,63A,100A
|
|
Pole
|
1,2,3,4P
|
|
Rated Impulse Withstand voltage
|
6000V
|
|
Short-time with stand current
|
20le
|
Time tolerance1s
|
Rated short-circuit the
ability to connect
|
30le
|
Making time ≥0.1s
|
Rated ability to connect
|
3le
|
|
Breaking capacity of rated limit short-circuit
|
3le
|
|
The number of on-load operation
|
2000
|
|
he number of no-load operation
|
10000
|
|
wiring capacity
|
50mm2
|
|
4.Working and installation condition
Normal working condition
Environment temperature : -5°C~+40°C, the average hours of temperature exceeding +35°C during 24 hours.
Elevation:≤2000m
No exceeding 50% at the maximum ambient temperature of 40°C.with lower temperature, higher humidity would be permitted, for example ,with temperature 20°C, the humidity can exceed 90%.Take the special measure to the dews on the surface, which would appear due to temperature change.
Pollution protection: Grade 2
Products should be used in no significant impact and vibration place.
Installation condition
Installing categories: ClassⅡ,Ⅲ(the level of over-load and distribution)
Installing condition: mounted by TH35-7.5 standard rail track.
Switches can be mounted vertically, can also be installed on the level.
5. Production line
Raw materials testing
Plastic shell processing
Coil winding processing
Magnet processing
Spring winding
Metal parts processing
Product assemble
Product testing