CE ROHS Tianshui 213 GSC1-FC series dust AC contactor
1.Application
1.Application
GSC1-4011FC~6511FC range dust AC contactor is used in AC 50Hz (or 60Hz), rated isolation voltage up to 690V, and rated current 40A~65A under rated voltage 380V and category AC-3 circuit, for long-distance making and breaking circuit, and can interoperable with the appropriate thermal overload relay comprising electromagnetic starter for protecting potential overload circuit. Adapt poor working conditions, larger environmental dust; require high-performance of dust industry, such as welding machine industry, the textile industry, cement factory, flour processing plants and so on.
2.Type
|
type
|
Power frequency Hz
|
coil voltage V
|
|||||
|
24
|
48
|
110
|
200
|
220
|
380
|
||
|
GSC1-4011FC~6511FC
|
50/60
|
B7
|
E7
|
F7
|
LC
|
M7
|
Q7
|
3.Structure Feature
Direct-moving, double breaking contact terminals;
Can added reverse device on both sides;
Can added auxiliary contact arrangement (F3-d)or air time-delay (SK4-2/3d);
Can added time-delay module, expanding module, over-voltage suppressor and other function model.
4.Working and installation condition
Ambient temperature: -5°C~+40°C; the average temperature ≤+35°C in 24h
elevation ≤2000m
Relative humidity is not exceeding 50% at the maximum ambient temperature +40°C. With lower temperature, higher humidity would be permitted. And average maximum relative humidity ≤90% in the most humidity month, at the same time, the average minimum temperature should ≤+25°C, and should give consideration to dews on the goods surface, which would appear due to temperature change;
Pollution grade: class 3;
Installation categories: class Ⅲ
Protection grade: IP50
Installation way: by screw.
5.Character
|
type
|
(AC-3 380V)
Rated work current A
|
Control power KW(AC-3)
|
Contact
volume
|
||||
|
220V
|
380V
|
415V
|
440V
|
660V
|
|||
|
GSC1-4011FC
|
40
|
11
|
18.5
|
22
|
22
|
30
|
3P+NO+NC
|
|
GSC1-5011FC
|
50
|
15
|
22
|
25
|
25
|
33
|
|
|
GSC1-6511FC
|
65
|
18.5
|
30
|
37
|
37
|
37
|
|
6.Technical parameters
|
type
|
GSC1-4011FC
|
GSC1-5011FC
|
GSC1-6511FC
|
||
|
Rated working current
le A(AC-3)
|
380V
|
40
|
50
|
65
|
|
|
660V
|
34
|
39
|
42
|
||
|
conventional thermal current
lth A
|
60
|
80
|
80
|
||
|
Rated working voltage Ue V
Rated working voltage
|
380,660
|
380,660
|
380,660
|
||
|
Rated insulation voltage Ui V
|
690
|
690
|
690
|
||
|
AC-3(6le, le)
|
life span of trip 104
|
50
|
50
|
50
|
|
|
Operation frequency h-1
|
600
|
600
|
600
|
||
|
AC-3(6le,6 le)
|
life span of trip 104
|
15
|
15
|
15
|
|
|
Operation frequency h-1
|
150
|
150
|
150
|
||
|
Rated working current le:A
|
380V
|
18.5
|
24
|
28
|
|
|
660V
|
9
|
12
|
14
|
||
|
Auxiliary contact
|
Conventional thermal current A
|
10
|
|||
|
Life span
|
AC-15(360VA)
|
With the main electrical contact life (AC-3)
|
|||
|
DC-13(33W)
|
|||||
|
Connect minimum load
|
24V,10mA
|
||||
|
Coil character
|
Rated control voltage
Us V
|
24,48,110,200,220,380
|
|||
|
pull voltage
|
0.85Us~1.1Us
|
||||
|
release voltage
|
0.2Us~0.75Us
|
||||
|
wiring power VA
50/60Hz
|
pull
|
230
|
|||
|
contain
|
26
|
||||
|
Machinery life span of trip times
|
500
|
||||