Product Main

Specifications

Product Description:
It is safe, non-pollute, and flame proof which can be installed directly on the load centre with the merits of free maintenance, easy installation, low combined operation cost, low loss and excellent humidity resistance. 
Technical Specifications
1. Voltage class: 6~35kV 
2. Model of voltage regulation: Off-excitation or on-load tap changer 
3. Tapping range: 5%, 2x2.5%, 
4. Power Capacity: 30-4000kVA 
5. Frequency: 50Hz or 60HZ 
6. Phase No.: Single phase or three phases 
7. Vector Group: Yyn0 or Dyn11 or according to customers' requirements 
8. Impedance voltage: 4~9% or according to customers' requirements 
9. Service condition: 100% relative humidity, ambient temperature not more than 40ºC or according to customers' requirements
10. Type of cooling: AN or AF 
11. Guard class: IP00, IP20, IP23 
12. Thermo-tolerance class of insulation: F 
13. Insulation level: A. For 10kV class: LI75AC35; B. For 35kV class: LI170AC70

Service conditions 
The height above the sea level is below 1000m 
Ambient temperature: 
Highest air temperature +40 degree
Highest daily average air temperature +30 degree 
Highest annual average air temperature+20 degree 
Lowest outdoor air temperature-25 degree 
Scope of application 
High-rise buildings, airports, terminals, power plants, transformer stations, residential areas or packages of various sites.

Technical Data of 10kV  SCB(9) Cast Resin F Insulation Class Dry Type Power Transformer
 
 
 
 
Loss(kW)
 
Insulation Level
Weight (kg)
Outline Dimension (mm)
Outline dimension with protective casing
Rated Capacity
Voltage Group(kV)
Connection Method
 
 (120℃)
No-load current
 
 
(L)
(W)
(H)
(L)
(W)
(H)
(kVA)
HV
LV
No-load
Load
%
 
 
 
 
 
10
 
 
 
0.15
0.325
4.5
 
130
600
450
490
900
800
850
20
 
 
 
0.185
0.63
4
 
170
600
450
560
900
800
850
30
 
 
 
0.215
0.75
3.2
 
330
620
450
650
1050
900
1000
50
 
 
 
0.305
1.055
2.8
 
380
620
450
750
1050
900
1000
63
 
 
 
0.37
1.28
2.7
 
440
750
500
760
1050
1000
1150
80
 
 
 
0.415
1.46
2.6
 
510
750
500
760
1100
1000
1150
100
 
 
 
0.45
1.665
2.4
 
590
750
500
890
1150
1100
1250
125
11
 
Dyn11
0.53
1.995
2.2
 
650
1060
600
1020
1350
1050
1200
160
10.5
0.4
 
0.61
2.25
2.2
F/F
780
1060
600
1060
1400
1050
1250
200
10
 
Yyn0
0.7
2.675
2
 
930
1060
710
1120
1450
1100
1350
250
6.3
 
 
0.81
2.92
2
 
1040
1100
710
1140
1500
1150
1400
315
6
 
 
0.99
3.67
1.8
 
1180
1150
710
1195
1500
1200
1450
400
 
 
 
1.1
4.22
1.8
 
1450
1260
870
1285
1600
1250
1600
500
 
 
 
1.305
5.17
1.8
 
1630
1290
870
1355
1600
1300
1650
630
 
 
 
1.51
6.22
1.6
 
1900
1450
870
1420
1800
1300
1700
630
 
 
 
1.46
6.31
1.6
 
1900
1500
870
1370
1850
1300
1650
800
 
 
 
1.71
7.36
1.6
 
2290
1550
870
1570
1900
1300
1800
1000
 
 
 
1.99
8.6
1.4
 
2700
1600
870
1665
1950
1300
1950
1250
 
 
 
2.35
10.26
1.4
 
3130
1680
1120
1765
2050
1350
2000
1600
 
 
 
2.755
12.42
1.4
 
3740
1750
1120
1860
2100
1400
2100
2000
 
 
 
3.735
15.3
1.2
 
4150
1770
1120
1865
2150
1500
2100
2500
 
 
 
4.5
18.18
1.2
 
4810
1870
1120
1950
2200
1500
2200
3150
 
 
 
5.78
23.7
1
 
5800
1950
1120
1900
2350
1600
2250
4000
 
 
 
6.7
28.5
1
 
7100
2100
1120
2050
2400
1600
2300
(Note): (Tapping range of high voltage) ±5%; ±2×2.5%, Frequency: 50Hz.
 
 
Technical Data of 10kV  SCB(10) Cast Resin F Insulation Class Dry Type Power Transformer
 
 
 
 
Loss(kW)
 
Insulation Level
Weight (kg)
Outline Dimension (mm)
Outline dimension with protective casing
Rated Capacity
Voltage Group(kV)
Connection Method
 
 (120℃)
No-load current
 
 
(L)
(W)
(H)
(L)
(W)
(H)
(kVA)
HV
LV
No-load
Load
%
 
 
 
 
 
10
 
 
 
0.135
0.305
4
 
130
600
450
490
900
800
850
20
 
 
 
0.17
0.595
3.5
 
170
600
450
560
900
800
850
30
 
 
 
0.195
0.705
2.6
 
330
620
450
650
1050
900
1000
50
 
 
 
0.27
0.995
2.2
 
380
620
450
750
1050
900
1000
63
 
 
 
0.33
1.21
2.2
 
440
750
500
760
1050
1000
1150
80
 
 
 
0.37
1.38
2.2
 
510
750
500
760
1100
1000
1150
100
 
 
 
0.4
1.57
2
 
590
750
500
890
1150
1100
1250
125
11
 
Dyn11
0.47
1.85
1.8
 
650
1060
600
1020
1350
1050
1200
160
10.5
0.4
 
0.545
2.13
1.8
F/F
780
1060
600
1060
1400
1050
1250
200
10
 
Yyn0
0.625
2.53
1.6
 
930
1060
710
1120
1450
1100
1350
250
6.3
 
 
0.72
2.76
1.6
 
1040
1100
710
1140
1500
1150
1400
315
6
 
 
0.88
3.47
1.4
 
1180
1150
710
1195
1500
1200
1450
400
 
 
 
0.975
3.99
1.4
 
1450
1260
870
1285
1600
1250
1600
500
 
 
 
1.16
4.88
1.4
 
1630
1290
870
1355
1600
1300
1650
630
 
 
 
1.345
5.87
1.2
 
1900
1450
870
1420
1800
1300
1700
630
 
 
 
1.3
5.96
1.2
 
1900
1500
870
1370
1850
1300
1650
800
 
 
 
1.52
6.955
1.2
 
2290
1550
870
1570
1900
1300
1800
1000
 
 
 
1.77
8.13
1.1
 
2700
1600
870
1665
1950
1300
1950
1250
 
 
 
2.09
9.69
1.1
 
3130
1680
1120
1765
2050
1350
2000
1600
 
 
 
2.45
11.73
1.1
 
3740
1750
1120
1860
2100
1400
2100
2000
 
 
 
3.32
14.45
1
 
4150
1770
1120
1865
2150
1500
2100
2500
 
 
 
4
17.17
1
 
4810
1870
1120
1950
2200
1500
2200
3150
 
 
 
5.14
22.5
0.8
 
5800
1950
1120
1900
2350
1600
2250
4000
 
 
 
5.96
27
0.8
 
7100
2100
1120
2050
2400
1600
2300
(Note): (Tapping range of high voltage) ±5%; ±2×2.5%, Frequency: 50Hz.