Product Main

Specifications

Function:
 
Provide sustainable power to other KNX equipments of the same line.
Short Circuit protection to other devices installed on the KNX line.
Protect other KNX devices by stabilizing input voltage and current.

Parameter:

Place of Origin Guangdong, China (Mainland)
Brand Name K-BUS
Model Number KP/D30.640.1
Input Voltage 95V ~255 V AC, 47~63Hz
Output Voltage 30V DC+-1V, SELV
Output Power Power loss: <6W
Output Current Rated Current: 640 mA, short circuit protection
Sustained Short Circuit Current Max. 1.3 A
Maintained Time after Power-off 200 ms
Operation Green LED indicate output voltage is ok
Display Red LED indicate overload or short circuit (I>Imax)
Installation on 35mm DIN rail
Connections EIB / KNX voltage output, via bus connection terminal (black/red)