1. Application
Rated insulation voltage: up to AC690V
Rated operational voltage: AC 380V or DC 220V
Protection grade: IP10
Standard: IEC60947-5
Certificate: CE, CCC
Warranty: 2 years
The top can be attached with Auxiliary contactor block or pneumatic time delay (extra option). The side can be attached with Auxiliary contactor block.
The coil terminal can be attached with time-delay device and amplifying device.
2.Working condition and installation condition
Ambient temperature: -25 to +60℃.
Humidity is up to 50% at +40℃ ambient temperature, and 90% at 20℃.
Site altitude: ≤3000m
Pollution degree: 3
Installation category: 3
Installation: The relays shall be installed with screws or mounted on 35mm DIN rail
3. Main technical parameters
|
JZC3-d series auxiliary relay
|
||||
Standard
|
IEC60947-5
|
||||
Insulation voltage (Ui) V
|
AC 690V
|
||||
Rated voltage (Ue) V
|
AC 380V, DC220V
|
||||
Rated thermal current (Ith) A
|
10A
|
||||
Rated current (Ie) A
(inductive load)
|
AC-15 (AC 380V)
|
0.95A
|
|||
DC-13 (DC 220V)
|
0.15A
|
||||
Minimum load
|
24V 10mA
|
||||
Operation frequency (times/h)
|
2400
|
||||
Mechnical life (104 times)
|
1000
|
||||
Electrical life (104 times)
|
1200
|
||||
Coil
|
Rated coil voltage (Us) V
|
Standard: 24V, 48V, 110V, 220V, 380V standard
|
|||
Pull-in voltage
|
0.85~1.1Us
|
||||
Drop-out voltage
|
0.2~0.75Us
|
||||
Pull-in power
|
70VA
|
||||
Hold power/ power consumption
|
8VA/ 1.8-2.7W
|
||||
Insulation insistance
|
10MΩ
|
||||
Withstand voltage
|
2500V, 1 minute
|
||||
Allowed instantaneous overcurrent
|
1 s
|
100A
|
|||
500 ms
|
120A
|
||||
100 ms
|
180A
|
||||
Wiring capacity
|
Flexible wire
|
1 or 2 wires
|
2.5mm
|
||
Hard wire
|
1 or 2 wires
|
4mm
|