Product Main

Specifications

1.   Application
JZC3-d series of Contactor Type Relay  is used in the control circuit of AC 50Hz/60Hz 380V or DC 220V, for the purpose of controlling electromagnetic coil, amplifying signal or transferring signal.
 Rated insulation voltage: up to AC690V
 Rated operational voltage: AC 380V or DC 220V
Protection grade: IP10                                                            
Standard: IEC60947-5
Certificate: CE, CCC
Warranty: 2 years
The top can be attached with Auxiliary contactor block or pneumatic time delay (extra option). The side can be attached with Auxiliary contactor block.
The coil terminal can be attached with time-delay device and amplifying device.
2.Working condition and installation condition
   Ambient temperature: -25 to +60℃.
   Humidity is up to 50% at +40℃ ambient temperature, and 90% at 20℃.
   Site altitude: ≤3000m
   Pollution degree: 3
   Installation category: 3
   Installation: The relays shall be installed with screws or mounted on 35mm DIN rail
 
3. Main technical parameters
                                     
JZC3-d series auxiliary relay
Standard
IEC60947-5
Insulation voltage (Ui) V
AC 690V
Rated voltage (Ue) V
AC 380V, DC220V
Rated thermal current (Ith) A
10A
Rated current (Ie) A
(inductive load)
AC-15 (AC 380V)
0.95A
DC-13 (DC 220V)
0.15A
Minimum load
24V 10mA
Operation frequency (times/h)
2400
Mechnical life (104 times)
1000
Electrical life (104 times)
1200
 
 
Coil
Rated coil voltage (Us) V
Standard: 24V, 48V, 110V, 220V, 380V standard
Pull-in voltage
0.85~1.1Us
Drop-out voltage
0.2~0.75Us
Pull-in power
70VA
Hold power/ power consumption
8VA/ 1.8-2.7W
Insulation insistance
10MΩ
Withstand voltage
2500V, 1 minute
 
Allowed instantaneous overcurrent
1 s
100A
500 ms
120A
100 ms
180A
Wiring capacity
Flexible wire
1 or 2 wires
2.5mm
Hard wire
1 or 2 wires
4mm