AC Power Source Single Phase Output
|
Introduction |
|
The TFC61 series are single phase output AC power source, output capacity from 500VA to 800kVA. Adopting PWM high frequency technology & IGBT regulation mode, the TFC61 series features constant frequency and voltage with high accuracy. The output is galvanically isolated. The TFC61 series can be used to simulate grids of different countries, widely used in laboratories, production calibration & test and military applications.
|
|
Features |
|
ü Output voltage: phase voltage 0-300V ü Output frequency: 47-63Hz, optional 400Hz ü Fast output key for 220V/50Hz, 110V/60Hz and 120V/60Hz ü Timing function, for output control 0~16 hours ü High accuracy LED display for voltage, current, frequency, active power, power factor ü Fast transient response, response time no more than 2ms for 100% load and unload ü Multiple protections: OVP, OCP, OTP and OLP ü Optional: RS-232/RS-485 interface for PC remote control on output frequency and voltage(TFC61 series) ü Customized specifications and functions acceptable
|
Specifications (1 phase in)
|
Model |
61005 |
6101 |
6102 |
6103 |
6105 |
6106 |
6110 |
|
|
Output capacity |
500VA |
1KVA |
2KVA |
3KVA |
5KVA |
6KVA |
10KVA |
|
|
Circuit mode |
IGBT/PWM |
|||||||
|
Input |
1φ2W, 220V±10% 50/60Hz |
|||||||
|
Output |
||||||||
|
Phase |
1 phase |
|||||||
|
Low range |
0V-150V |
|||||||
|
High range |
0V-300V |
|||||||
|
Frequency |
50Hz, 60Hz, 47-63Hz, optional 400Hz |
|||||||
|
Max. current |
0V-150V |
4.6A |
9A |
18A |
27A |
45A |
54A |
90A |
|
0V-300V |
2.3A |
4.5A |
9A |
13.5A |
22.5A |
27A |
45A |
|
|
Frequency regulation |
≤0.1% |
|||||||
|
Load regulation |
±1.5% |
|||||||
|
Harmonic distortion |
±2% (resistive load) |
|||||||
|
Response time |
Max. 2ms |
|||||||
|
Efficiency |
≥80% (>3kW) / ≥70% (≤3kW) |
|||||||
|
Meter & Resolution |
||||||||
|
Frequency meter |
4 digits LED, resolution 0.1Hz |
|||||||
|
Voltmeter |
4 digits LED, resolution 0.1V |
|||||||
|
Ammeter |
4 digits LED, resolution 0.001A (<4A) / 0.01A (>4A) |
|||||||
|
Power meter |
4 digits LED, resolution 0.1W (<200W) / 1W (>200W) |
|||||||
|
Power factor meter |
4 digits LED, resolution 0.001 |
|||||||
|
Protection |
Fuse switch for input and output; Fast-response circuit to detect over voltage, over current, over load, over temperature and short circuit; Output will be shut down in protection mode. |
|||||||
|
Cooling |
Cooling fan |
|||||||
|
Operation environment |
0℃-45℃, ≤90% RH(Non-condensing), Altitude: 1500 feet |
|||||||