Equipment use
Axial flow vertical air curtain is air circulation heating unit with output nozzle, suit not more than 6 metres high building factory gate.
You must abide by conditions strictly implement the production business requirements and installation of rules, including the test run, the formal operation and maintenance (in accordance with the operation manual requirements), and consider the possible fault and danger.
Matters needing attention
Installation operation and maintenance of the axial flow vertical ventilation unit maintenance must be trained, familiar with the installation instructions, and a full understanding about the possible dangerous situations.
Axial flow vertical warm air curtain ventilated unit with operating mode the following:
1 The internal air circulation heating mode of the fan operating low speed conditions.
1 The internal air circulation heating mode of the fan operating high speed conditions.
1 Standby mode
1 Shutdown mode
Must comply with the "technical data" provided scope and limits.
Any loss due to the use of do not follow the above provisions, the manufacturer shall not be liable for any
! The ventilation unit are not suitable for installation at explosible gas, high humidity and dust high architectural environment.
Dangerousness
Despite all of the dangerous situation that may arise to take preventive measures, but there still exists some not typical problems need to be paid attention:
When using electrical system should pay attention to the danger of electric shock .
On the axial flow vertical ventilation air curtain unit tool is possible to fall from a height when installed.
The device damage caused by component failure.
When using the heating system,pay attention to the possibility of being scalded.
Structure and function
Axial flow vertical air curtain is air circulation heating unit with output nozzle, suit not more than 6 metres high building factory gate.A plurality of axial flow vertical ventilation warm air curtain unit is fixed above the entrance, absorb indoor air , and use the built-in gas and water heat exchanger heating the air, and then transport through the output nozzle. Air curtain machine influence on the indoor climate minimum, effectively prevent the intrusion of cold air at the same time to increase the indoor use of space.
Due to the use of highly efficient and powerful air distribution device, axial flow vertical ventilation warm air curtain unit can cover a large area, compared with other system can effectively reduce the amount of ventilation unit to save cost.
According to different requirements of different customers, we can provide three kinds of equipment of different models for you option. Fan of each model has two different speed. Variety of accessories to fully meet customer requirements. Heat medium is hot water. But also can according to the customer request custom made steam or electric heating unit.
Equipment structure
Axial flow vertical warm air curtain ventilation unit comprises the following components: heating unit (heat exchanger and fan) and an output nozzle. These two parts are screwed to the ventilation unit.
1 shell: cold-rolled steel plate, the surface is electrostatic spraying
2 fan: low energy consumption of axial fan, low noise, no need of maintenance
3 heat exchanger: heat exchanger is consists of copper tube and aluminum fins, or adopt the electric heater use for heating, or adopt specially steam heat changer for heating.
4 air supply nozzle
The maximum operating pressure: 116PSIG
The highest heating medium temperature: 248℉
The highest supply air temperature: 140℉
The maximum ambient temperature: 104℉
4 system design
When tall building indoor ventilation system design , shoud pay special attention to the internal impact by the open door building. Because without design protection door leads to the energy loss and the destruction of the indoor comfort degree. Therefore, for this situation of air curtain machine is very important (see chart)
! In general, the running environment of air curtain machine shall be a slight positive pressure of the indoor environment, this condition can be achieved by installing additional fresh air or wind mixing unit.
Selection principle
Through a selection principle to choose air curtain machine model, it is through the following several conditions to calculate the number of the corresponding gate size need air curtain machine.
1 The required air flow rate through the door size, indoor and outdoor air density difference and velocity calculated.
1 Between the two air curtain machine distance cannot exceed the width of the equipment of 3/4
1 An air flow cross section must be higher than the door half high
Rapid selection
The following picture (picture 6-1) can be used to quickly select simple, the data is provided in the outdoor temperature 3.2℉ indoor temperature of 68℉.
The different sizes of the gate required different number of air curtain machine.
Transportation and installation
!Transportation and installation of the equipment can only be carried out by experts
In the process of transportation and installation may need lifting equipment or scaffold, do not tilt equipment and shelve heavy object on equipment.
Installation
First check the connection of the heat exchanger and the outlet nozzle is in the corresponding position, if not, loosen joint nozzle and the heat exchange part, the position of the nozzle in accordance with the requirements of fixed.
In order to fixed on the ceiling, the equipment unit should be using M8 six angle screw fixed nut and inner six angle screw and standard gasket.
! The fixing nut is designed for the weight of the equipment design, please do not add additional load on the device.
! Fixed nut can not be with the bending action, so please don't use a fixed eye rings.
! The equipment after it is installed, it must maintain a balance.
Piping system installation
!The installation of the pipeline on hydronic systems can only be by the the experts to conduct
1 Combined ventilation units are running in the same working conditions (room temperature, the heat, the running time and so on) and a controller
1 Low or medium pressure, water temperature is not more than 248℉ can be used as heating medium. For the purpose of energy saving, the water distributor shall advance heat calculation, which can ensure that each heat exchanger heat energy needs can be met
1 The addition of a separate air heat exchanger is also possible, but must be considered into the backwater pipeline pressure compensation, lateral balance, and the need to add additional pipeline
! Unable to bear other loads, such as: heat exchanger directly communicated with the return pipe.
Independent ventilation unit must ensure that in the control region temperature the hydraulic balance.
Circuit connection
! Circuit connected only by the corresponding electrical experts must comply with local regulations.
1 Before delivery has ventilation unit running ready
1 Check all use ofsupply voltage, whether the fuse voltage accord with requirements (in equipment nameplate can be found on the corresponding data), if any one can not meet the requirements, the equipment can not be connected
1 When using long distance connection circuit needs to check whether it meets the requirements of the cable diameter
1 Should according to the wiring diagram to connect the circuit connection.
1 Thermal relay in the motor need to be connected, otherwise will not be able to start the motor overheating protection device
1 Don't forget the whole system installed a main switch
1 A plurality of ventilation unit can marshalling operation
1 The control valve of thermal protection relay and the single equipment must be installed.
|