Product Main

Specifications

 Outdoor AC High Voltage Switch Disconnectors

Description & Application

The series product is a three-phase alternating current frequency 50Hz/60Hz outdoor high voltage transmission equipment. It is suitable for installing in outdoor high voltage distribution equipment line. It is used to break and close three-phase circuit without load, which has obviously isolating distance.

Technical Parameter & Detail Show
Technical Parameter



Insulator Material Porcelain
Rated Voltage(kV) 12
Rated Current(A) 200, 400, 630, 1000, 1250
Rated Frequency(Hz) 50Hz/60Hz
Rated Short-Time Withstand Current (kA/S) 25kA, 20kA, 16kA/4S
Rated Peak Withstand Current 50kA
Rated Lightning Impulse Withstand Voltage (kV) 80(Phase to Earth)
90(Across Isolating Distance)
Rated Power Frequency Withstand Voltage(kV) 45(Phase to Earth)
55(Across Isolating Distance)
Operation Mechanism Model CS01-D(Earthing)
CS12(Earth-Free)
Material

The main parts include terminal palms, fixed & moving contact, operating arm insulator, insulator post, operating arm, axis of rotation and rotating lever and so on.

Terminal palms

Terminal palm is composed of rotation and frame with angle steel welded, which have six insulators, two sets for a pole. Three-phase operation insulators which operate the knife close or open are installed on the axis of rotation. Operating arm drives axis of rotation to make the separate the knife from contacts when it opens. It even drives axis of rotation to make the insulator pull the knife move down and rotate to closed position when it closes.

Application Conditions

1 Ambient Temperature: -40℃~+50℃

2 Elevation: ≤2,000m

3 Seismic Intensity: ≤8

4 Maximum Wind Speed: 35m/s

 
Standards

IEC62271-102

GB 1985-2004

GB/T11022-1999

DL/T 486

DL/T 593

Service
 
Shipping

1 Sea Way

2 Air Way

3 Express

Payment

1 PayPal

2 West Union

3 Wire Transfer

4 T/T