AC Outdoor MV Fuse

Description & Application

SSOC series of wind field 12kV & 40.5kV outdoor AC high voltage drop-out fuse cutout is a kind of overload protection device, which is most suitable for using in wind field, power station, etc. It is installed on the high voltage side of distribution transformer or distribution wire pole. The device is used in transformer & line, for short-circuit protection, overload protection and load current on/off.

Technical Parameter

Item Data
Rated Voltage 40.5kV
Rated Continuous Operating Current 100A,200A
Rated Frequency 50Hz/60Hz
Rated Fuse Base Current 100A,200A
Rated Short-circuit Breaking Current 8kA, 10kA(4time for 100A, 1time for 200A)
Rated Power Frequency Withstand Voltage  100kV/80kV(dry/wet)
Rated Lightning Impulse Withstand Voltage  185kV/200kV(phase to earth/across isolating distance)
Creepage-distance 1256mm(silicone rubber)
Mechanical Life 500times(continuous switch on- off)
Elevation 2000m
Ambient Temperature -40 ~ +70
Working Principle

Firstly, insulator, upper & lower fixed parts, installation structure & material have been improved to avoid that the product's shaking leads to fuse tube false dropout. In the meanwhile, the installation angle is adjusted to horizontal from 15~30°.

Secondly, the contact way of moving contact & fixed contact has been improved. Concerning the common product, usually, its upper conductive plate contacts with the dome by compression spring pressure, which in bad whether will easily cause false dropout because of shaking, spring non-effect, conductive part too hot, etc. Therefore, except the common way the bayonet coupling contact way is also added, with these two ways it can stand a wind of 50m/s.

Finally, the operation and installation method have been optimized, the normal off/on operation is the same with common fuse cutout, but when it dropouts, only the moving contact fixed in fuse tube will dropout, the upper contact & upper conductive plate will still keep in touch, because the moving contact is nested with upper contact. Therefore, it should drop down the upper contact with insulated rod before replacing the fuse link

Application Conditions

Ambient Temperature: -40℃~+70℃

Elevation: ≤2000m

Rated Power Frequency: 50Hz/60Hz;

Seismic Intensity: ≤8
Max. Wind Speed: 50m/s
 
Standard
GB 311.1-2012
GB/T 11022-2011
GB/T 15166.3-2008
DL/T 593
DL/T 640
IEC 60071-1
IEC 62271-1: 2007
IEC 60282-2
ANSI C37.41
ANSI C37.42
 