Outdoor AC High Voltage Vacuum Circuit Breaker
 
Description & Application
 
The product is designed according to the most advanced international ideas: the APG coating silicone rubber insulation technology of epoxy resin is used on the pole of vacuum arc-extinguishing chamber. The main application is to protect and control the distribution network of substation, mine industries, town and country and so on.
 
Technical Parameter & Detail Show
Technical Parameter
 
Item
Unit
Data
Rated Voltage
kV
12
24
Rated Insulation Level
1 min Power Frequency Withstand Voltage(Dry/Wet)
kV
42(Across isolating distance 49)/34
65(Across isolating distance 79)/52
Lightning Impulse Withstand Voltage (Peak)
75(Across isolating distance 85)
125(Across isolating distance 145)
Rated Current
A
630
1250/630
Rated Short-Circuit Breaking Current (Peak)
kA
20
25
Rated Short-Circuit Making Current (Peak)
50
60
4s Rated Short-Time Withstand Current
20
25
Rated Peak Withstand Current
50
60
Rated Operating Sequence
 
Off-0.3s-On/Off-180s-On/Off
Off-0.3s-On/Off-180s-On/Off
Breaking Times of Rated Short-Circuit Breaking Current
times
30
30
Times of Mechanical Life
10000
10000
Rated Operating Voltage
V
(DC, AC)220
(DC, AC)220
Operating Mode
 
Spring Operation (Electric/Manual)
Spring Operation (Electric/Manual)
Outline Dimension
mm
945×420×745
1200×600×950
Weight
kg
60
150
Notes: When using the product at the place where is above 1000m of sea level, relative amendment should be made on insulation withstand voltage which according to standard GB/T 11022.
 
Material
 
The Configuration of Current Transformer
 
External current transformer works as protection, with the transformation ratio 50/5600/5 and the standard configuration is 2pcs. The maximum quantity is 6pcs (one group is for measurement, the other group is for protection). Once the requirement of measuring winding precision is above level 0.5, the transformation ratio is 200/5,300/5,400/5,600/5.

Operating Power Supply
 
The operating supply is from the AC/DC low-voltage 220V (110V) provided by users or from the secondary voltage of AC 220V (110V) output by the voltage transformer (external) connected to the 10kV overhead line. For the purpose of convenient installation, the outdoor type voltage transformer with fuse protector is recommended.
 
Application Conditions
 
1 Ambient Temperature: -45℃~+40℃
2 Range of Daily Temperature: ≤25℃
3 Wind Speed: ≤35m/s
4 Elevation: ≤1000m
5 Seismic Intensity: ≤8 degrees
6 Ambient Humidity: Monthly value of relative humidity ≤90%, daily average value of relative humidity ≤95%
7 Thickness of Ice: ≤20mm
8 Application Site: No danger of inflammability and explosion, chemical corrosion or violent vibration.
 
Standards
 
IEC 56
GB 1984
GB/T11022
DL/T 615