Product Main

Specifications

Outdoor Pole-mounted HV Vacuum Load Break Switch
 
Description & Application
 
PVS2-12 outdoor pole-mounted HV vacuum load break switch uses vacuum arc-extinguishing chamber to extinguish arc, with no danger of explosion and no need of overhaul. The isolation knife of the electrical load break switch makes parallel connection with three-pole vacuum arc-extinguishing chamber, with good on-off operating simultaneity; and when it is off, there is a reliable isolating breaking point, with the same function to disconnector. It is suitable for substation, industrial and mining enterprises for urban & rural network as protection and control, as well as urban and rural automatic distribution network and the sites for frequent operation.
 
Technical Parameter & Detail Show
Technical Parameter

 
Item Unit Data
Rated Voltage kV 12
Rated Current A 630
Rated Frequency Hz 50
Rated Peak Withstand Current (Peak) kA 40
Rated Short-time Withstand Current (Peak) kA 40/3 times
Breaking Rated Active Load Current A 630/100 times
Breaking 5% Rated Active Load Current A 31.5/20 times
Breaking Rated Cable Distribution Line Closed-loop Current A 630/10 times
Breaking Rated Cable Charging Current A 10/20 times
Rated Short-time Withstand Current kA 16/4s
Rated Operation Voltage V 220(DC.AC)
Auxiliary Circuit Rated Voltage V 220(DC.AC)
Operating Mode   Spring Operation (Manual/Electric)
1min Power Frequency Withstand Voltage(Dry/Wet) kV 42(Across the Isolating Distance 49)/30
Lightning Impulse Withstand Voltage(Peak) kV 75(Across the Isolating Distance 86)
Overall Dimensions (Width*Depth*Height) mm 700*222*642
Weight kg 60

 
Material
 
Main parts of vacuum load switch are made of stainless steel, while its bracket uses stainless steel or hot galvanizing and ultravoiolet ray-proof coating followed for the effective prevention of corrosion and rust, ensuring the normal conduction of switchgear under outdoor conditions. Switch knife uses pressure spring, ensuring enough pressure, contributing to the convenient operation and the reliability of on-off operation. The load break switch opens/closes under rated load voltage, with no requirement of 2-time protection device connection.
 
Application Conditions
 
1 Ambient Temperature: -40℃~+55℃, Daily Temperature Difference: ≤25℃
2 Max Wind Speed: ≤ 35m/s
3 Elevation: ≤1000m, Seismic Intensity: ≤8
4 Humidity: ≤90% for Monthly Average Humidity, ≤95% for Daily
5 Thickness of Covering Ice: ≤20mm
6 Application Site: No danger of inflammability and explosion, chemical corrosion or violent vibration.
 
Standards
 
GB 3804
GB/T 11022
GB 311.1
GB 3309
GB 4208
DL/T 884
GB 50150
Service
 
Shipping
 
1 Sea Way
2 Air Way
3 Express
 
Payment
 
1 PayPal
2 West Union
3 Wire Transfer
4 T/T
 
We’re always at your service, any question feel free to contact us.