| Type: | Earth Leakage,AC |
|---|---|
| Certification: | Earth Leakage,AC |
| Poles Number: | 1P+N,4 |
| Rated current: | 6,10,16,20,25,32A |
| Curve: | C |
| Mechnical Life: | 4000t |
| Electrical Life: | 2000t |
Quick Details
Specifications
Specifications
Overload Trip Characteristic
1)DZ30LE Earth Leakage Circuit Breaker
2)Output:5000pcs/day
3)Standard: IEC/EN 61009-1
4)OEM;
5)CE,CB;ISO9001,14001,IEC
2)Output:5000pcs/day
3)Standard: IEC/EN 61009-1
4)OEM;
5)CE,CB;ISO9001,14001,IEC
DZ30LE Earth Leakage Circuit Breaker
DZ30LE is used in the single phase residence circuit of AC 50Hz/60Hz,rated voltage 230V,used as electron shock protection.It can protect civil electron circuit form overload and short circuit This product has advantages of small volumn,high breaking capacity zero,and live wire are cut off at the same time,also protecting person from electric shock when the live wire connected opposite.This product conforms to IEC61009,GB16917 Stardands.
Main Technical Paramete
|
Rated
current (A) |
No.of
pole |
Rated
voltage (V) |
Rated current of
frame |
Rated leakage
operating |
Rated leakage non-operating current
|
Rated
leakage breaking time |
Breaking
capacity (A) |
|
6,10,16,
20,25,32 |
1+N
|
230
|
32
|
30
|
15
|
≤0.1s
|
3000
|
Overload Trip Characteristic
|
Rated
current(A |
Rated
voltage(A) |
Limited
time |
Pre-engage
result |
Start state
|
Note
|
|
1.13In
|
all
|
t≥1h
|
non-trip
|
cold state
|
|
|
1.45In
|
all
|
t<1h
|
trip
|
heat state
|
he current rise steadily to a fixed #118alue within 5s
|
|
2.55In
|
all
|
1
|
non-trip
|
cold state
|
|
|
5In
|
all
|
t≥0.1s
|
trip
|
old state
|
Open the supplementary switch,connect the power
|
|
10In
|
all
|
t<0.1s
|
trip
|
old state
|
Open the supplementary switch,connect the power
|