Product Main

Quick Details

Type: Moulded Case
Standard: IEC 60947-2
Current: 63,125,160,250,400,630,800,1250
Rated operating voltage: 690V
Poles Number: 2,3,4
Rated insulation operating voltage: 950
Certification: CE ISO9001

Specifications

Specification Detail
 
Rated current of
release (A)
Thermodynamic release (ambient temp+40°C) Operational current
of magnetic release (A)
1.05In (cold state)
inoperative time (h)
1.30In (heat state)
inoperative time (h)
In ≤ 63 ≥ 1 < 1 10In±20%
63 < In ≤ 100 ≥ 2 < 2 10In±20%
100 < In ≤ 630 ≥ 2 < 2 5-10In±20%
 
Rated Current of
Release (A)
Thermodynamic release (ambient temp+40°C) Operational current
of magnetic
release (A)
1.0In
(cold state)
inoperative
time
1.20In
(heat state)
operative
time
1.50In
(heat state)
operative
time
7.2In (heat
state)
operative
time
12.5 ≤ In ≤ 400 ≥2h <2h ≤4min 2S<Tp≤10S 12In±20%
 
 
Type Rated
current(A)
Poles Rated
insulation
voltage(V)
Rated
operating
voltage(V)
Arcing
over
distance(mm)
Ultimate
short
circuit
breaking capacity
Servies
short
circuit
breaking
capacity
Operating
performance
(times)
ON OFF
NF-100D 12.5,16,
20,25,32,
40,50,63,
80,100
3,4 950 690 0 18 18 1500 8500
NF-100N 25 25
NF-100H 70 70
NF-160D 16,20,25,
32,40,50,
63,80,100,
125,160
25 25 1500 7000
NF-160N 36 36
NF-160H 70 70
NF-250D 160,180,
200,225,
250
25 25 1000 7000
NF-250N 36 36
NF-250H 70 70
NF-400D 200,225,
250,300,
315,400
35 35 1000 4000
NF-400N 45 45
NF-400H 70 70
NF-630D 315,350,
400,500,
600,630
35 35 1000 4000
NF-630N 45 45
NF-630H