Electricity Type: | AC |
---|---|
Main Circuit Rating Voltage: | 1000V |
Maximum rated current for motor control : | 115A -630A |
Phase: | 3 |
Number of Pole: | 3 |
Certificate: | CE,CCC |
Quick Details
Specifications
Specifications
CJX2-F(LC1-F) AC Contactor /Contactor Electrical /Electrical Contactor
1)CE,CB,ISO9001,14001
1)CE,CB,ISO9001,14001
CJX2-F(LC1-F) AC Contactor /Contactor Electrical /Electrical Contactor
General:
CJX2-F series AC contactor is applicable in the circuit rated voltage up to 1000V AC. 50/60Hz, rated current up to 781A, for long distance breaking curcuit and frequency starting or controlling the motor. It also can be used for the control of distributing ciurcuits of rated current from 200A to 1600A(AC-1)/115A to 780A(AC-3). The products cmply with IEC 60947-4.
Type
|
CJX2-F115
|
CJX2-F150
|
CJX2-F185
|
CJX2-F225
|
CJX2-F265
|
CJX2-F330
|
CJX2-F400
|
CJX2-F500
|
CJX2-F630
|
||
Main circuit characteristic
|
|||||||||||
Poles
|
3P.4P
|
||||||||||
Rated operation voltage (Ue
|
V
|
380,660,1000
|
|||||||||
Rated insulation voltage (Ui
|
V
|
1000
|
|||||||||
Rated heating current (Ith)
|
A
|
200
|
200
|
275
|
275
|
315
|
380
|
450
|
630
|
800
|
|
Rated operation current (Ie)
|
AC-3 380V
|
A
|
115
|
150
|
185
|
225
|
265
|
330
|
400
|
500
|
630
|
AC-3 660V
|
A
|
86
|
108
|
118
|
137
|
170
|
235
|
303
|
353
|
462
|
|
AC-3 1000V
|
A
|
46
|
51
|
71
|
90
|
112
|
115
|
200
|
232
|
331
|
|
AC-4 380V
|
A
|
52
|
60
|
79
|
85
|
105
|
117
|
138
|
147
|
188
|
|
AC-4 660V
|
A
|
49
|
61
|
69
|
82
|
98
|
118
|
135
|
145
|
170
|
|
Max.power of 3 phase motor controlled
|
AC-3 220V
|
Kw
|
30
|
40
|
55
|
63
|
75
|
100
|
110
|
147
|
200
|
AC-3 380V
|
Kw
|
55
|
75
|
90
|
110
|
132
|
160
|
200
|
250
|
335
|
|
AC-3 660
|
Kw
|
80
|
100
|
110
|
129
|
160
|
220
|
280
|
335
|
450
|
|
Electrical life
|
AC-3
|
10000t
|
60
|
50
|
30
|
20
|
|||||
AC-4
|
10000t
|
1.5
|
1.5
|
0.8
|
0.5
|
||||||
Machinery life
|
10000t
|
600
|
600
|
500
|
500
|
||||||
Operation Frequency
|
AC-3
|
t/h
|
600
|
600
|
300
|
300
|
|||||
AC-4
|
t/h
|
150
|
150
|
150
|
150
|
||||||
Matching fuse type
|
RT16-160
|
RT16-200
|
RT16-250
|
RT16-315
|
RT16-400
|
RT16-400
|
RT16-500
|
RT16-630
|
RT16-800
|
||
Matching thermal relay type
|
LR9-F53
|
LR9-F73
|
|||||||||
Wiring capacity
|
mm²
|
50
|
50
|
95
|
95
|
150
|
185
|
30X5(2)
|
40X5(2)
|
50X5(2)
|
|
Coil
|
|||||||||||
Control power voltage (Us)
|
AC
|
V
|
48,110,220,380,440,660,
|
||||||||
Allowed control circuit voltage
|
Close
|
V
|
85%~110%Us
|
||||||||
Open
|
V
|
20%~75%Us(AC)
|
|||||||||
Coil power
|
Close
|
VA
|
550
|
800
|
1200
|
1200
|
1250
|
1650
|
|||
Keeping
|
VA
|
45
|
55
|
13
|
20
|
24
|
22
|
||||
Loss power
|
W
|
12~16
|
18~24
|
12
|
14
|
18
|
20
|
||||
Auxiliary contact
|
|||||||||||
Rated heating current (Ith)
|
A
|
10
|
|||||||||
Rated operation voltage (Ue)
|
AC
|
V
|
380
|
||||||||
DC
|
V
|
220
|
|||||||||
Rated control capacity
|
AC-15
|
VA
|
360
|
||||||||
DC-13
|
W
|
33
|
Ambient temperature
|
-5~+40
|
Altitude
|
≤2000m
|
Relative humidity
|
The maximum temperature of 40 degrees, the air relative humidity not exceed 50%, at a
lower temperature can allow for a higher relative humidity, if humidity changes as a result
of occasional gel generated,should eliminate it.
|
Pollution level
|
3
|
Installation category
|
III
|
Installation position
|
The installation degree of the tilt and vertical plane should not exceed ±22.5°,
should be installed in place with no significant impact shaking and vibration
|
Install
|
|