Condition: | New |
---|---|
Type: | Natural Circulation |
Usage: | Industrial |
Structure: | Water and fire tube |
Pressure: | Low Pressure |
Style: | Horizontal |
Place of Origin: | China (Mainland) |
Brand Name: | EPCB |
Model Number: | DZL1-30T |
Output: | Hot Water |
Dimension(L*W*H): | 4876*1800*2870mm |
Weight: | 13.5t |
Certification: | |
After-sales Service Provided: | Overseas service center available |
Quick Details
Specifications
DZL series single drum coal fire hot water boiler
1. signle durm design
2. boiler capacity of 1-35T/H
1. signle durm design
2. boiler capacity of 1-35T/H
DZL series coal fired hot water boiler
* This thread boiler smoke pipe, arch tube sheet, wing flue structure, is the first victory in national development and National patent in 1991, after nearly two decades of continuous improvement and perfection of its structure is more reasonable, environmentally friendly energy.Effects become more prominent.
* for the application of different fuels, chain grate and reciprocating grate is divided into two series. With energy, strong radiation arch, can be applied to all types of bituminous coal combustion.
* with high standards, high-quality auxiliary equipment, accessories, automated control to ensure the boiler is safe, stable.
* Compact ,1-10T / H fast assembly ,15-35T / H large assembly, single-layer arrangement, one-time investment province.
* boiler capacity of 1-35T / H (0.7-29MW).
* for the application of different fuels, chain grate and reciprocating grate is divided into two series. With energy, strong radiation arch, can be applied to all types of bituminous coal combustion.
* with high standards, high-quality auxiliary equipment, accessories, automated control to ensure the boiler is safe, stable.
* Compact ,1-10T / H fast assembly ,15-35T / H large assembly, single-layer arrangement, one-time investment province.
* boiler capacity of 1-35T / H (0.7-29MW).
Item\Type | DZL0.7-0.7/95/70-A II | DZL1.4-0.7/95/70-A II | DZL2.1-0.7/95/70-A II | DZL2.8-0.7/95/70-A II | DZL4.2-1.0/115/70-AII | DZL5.6-1.0/115/70-AII | DZL7.0-1.0/115/70-A II | DZL10.5-1.0/115/70-AII | DZL14-1.25/130/70-AII | DZL21-1.25/130/70-AII | |
Rated capacity MW | 0.7 | 1.4 | 2.1 | 2.8 | 4.2 | 5.6 | 7.0 | 10.5 | 14 | 21 | |
Rated working pressure Mpa | 0.7 | 0.7 | 0.7 | 0.7 | 1.0 | 1.0 | 1.0 | 1.0 | 1.25 | 1.25 | |
Supply water temperature C | 95 | 95 | 95 | 95 | 115 | 115 | 115 | 115 | 130 | 130 | |
Return water temperature C | 70 | 70 | 70 | 70 | 70 | 70 | 70 | 70 | 70 | 70 | |
Circle flow m3/h | 24 | 48 | 72 | 96 | 80 | 106 | 133 | 200 | 200 | 300 | |
Heated area M2 | radiation/convection | 4.55/20.12 | 6.2/39.5 | 6.7/54.2 | 7.81/65 | 15.2/92.38 | 22.3/159.5 | 19.5/207.6 | 23.5/282 | 34.36/408.51 | 76/601.6 |
Heat efficiency % | 76 | 77 | 82 | 78 | 78 | 80.5 | 80.6 | 80.48 | 81 | 81.87 | |
Fuel consumption kg/h | 175 | 346 | 487 | 684 | 1025 | 1325 | 1655 | 2485 | 3290 | 4653.3 | |
effective area of grate m2 | 1.8 | 2.7 | 3.58 | 5.14 | 8 | 10.9 | 12 | 17.81 | 22.51 | 26.88 | |
size of transportation mm | length | 4876 | 5019 | 5950 | 6510 | 7000 | 7486 | 7600 | 8600 | 7810 | 8650 |
width | 1800 | 2130 | 2200 | 2600 | 2950 | 3160 | 3200 | 3373 | 3370 | 2450 | |
heigth | 2870 | 3222 | 3410 | 3520 | 3938 | 3354 | 3660 | 3160 | 3500 | 2594 | |
weight of transportation ton | 13.5 | 18.5 | 23.6 | 26.5 | 35 | 30 | 44 | 22 | 25 | 26.6 | |
* Notes: This form only for your reference,if any changed,please refer to Ex-factory technical documents. |