Product Main

Quick Details

Place of Origin: China (Mainland)
Brand Name: GOLD
Model Number: GDVA-404

Specifications

1.1 Application

Tests for current transformer:
1)Excitation curve and parameters test
2)Turns ratio test
3)Ratio and phase error test
4)Polarity mark check
5)Coil resistance measurement
6)Secondary loop burden measurement
7)Error line curve test for protection CT
8)Transient CT parameters test
9)CT nameplate guess
10)Saturation hysteresis loop curve measurement

Tests for voltage transformer:
1)Turns ratio test
2)Polarity test
3) Secondary burden test
4) Coil resistance test

 

Applications for CT PT Tester:
1) CT nameplate check
2) CT parameters check in work burden
3) CT transient parameters analysis
4) CT ratio and phase error calibration
5) PT routine test


1.2 CTPT analyzer technical index
1.   Test standards: IEC60044-1, IEC60044-6, GB1208, GB16847, C57.13
2.    Power supply: AC220V±10%,50Hz/60Hz±10%
3.    Power output: 0.1~125V (AC)
4.    Current output: 0.001~5A(RMS)
5.    Power output:300VA
6.    Maximum knee voltage measurement:45kv
7.    Current measurement:
       Range:0~10A (automatically change range in 0.1/0.4/2/10A) 
       Error <±0.1%+0.01%FS
8.    Voltage measurement:
       Range:0~200 V (automatically change range in 1V/10V/70V/200V)
       Error < ±0.1%+0.01%FS
9.    Turns ratio measurement:
       Range :1~30000,
       1~2000 error<0.05%
       2000~5000 error>0.1%
       5000~30000 error<0.2%
10.  Phase measurement: error:±2min,resolution:0.01min
11.  Coil resistance measurement:
       Range:0~8kΩ (automatically change range in 2ohm/20ohm/80ohm/800ohm/8kohm)
       Error< 0.2%RDG+0.02%FS
       Maximum resolution:0.1mΩ

12.  Temperature measurement:-50~100 Celsius degree, error<3 Celsius degree
13.  CT Secondary burden:
       Range 0~160ohm (automatically change range in 2ohm/20ohm/80ohm/160ohm)
       Error <0.2%RDG+0.02%FS
       Maximum resolution 0.001ohm
14.  PT Secondary burden:
       Range 0~80kohm (automatically change range in 800ohm/8kohm/80kohm)
       Error <0.2%RDG+0.02%FS
       Maximum resolution: 0.1ohm
15.  PT ratio measurement:
       Range :1~30000,
       1~5000 error<0.2%
       5000~30000 error<0.5%
16.  Saved data groups:>1000groups
17.  Work condition: Temperature:-10°C~50°C, moist:≤90%
18.  Size: 485mm×356mm×183mm
19.  Weight: <15Kg