| Place of Origin: | China (Mainland) |
|---|---|
| Brand Name: | SEA |
| Model Number: | CG103-12 |
| Material: | Composite Polymer |
| Application: | High Voltage |
| Rated Voltage: | 17.5kV |
Quick Details
Specifications
Voltage sensor
Voltage measurement in CG sensors is based on the resistive divider principle.
Sensor application
The voltage sensor type CG is intended for use in voltage measurement in air insulated medium voltage switchgear. The voltage sensor KEVA B has been designed to be used as a post insulator but can be used as a stand-alone unit as well.
Application of voltage sensor as a post insulator in air insulated medium voltage switchgear UniGear ZS1.
Differences between Sensors and Instrument Transformers
There are some noticeable differences between Sensors and conventional Instrument Transformers:
Standards
Voltage sensors:
IEC 60044-7 (1999-12)
Instrument transformers –Part 7: Electronic voltage transformers
Highest voltage for equipment and test voltages
Highest voltage for equipment, Um: 17.5 kV
Rated power frequency test voltage: 38(42) kV
Rated lightning impulse test voltage: 95 kV
Note: For CG12 the extended rated power frequency test voltage 42kV could be selected.
Voltage sensor, rated values
Rated primary voltage, Upn: 15/√3 kV
Rated frequency, fr: 50/60 Hz
Accuracy class: 0.5/3P
Rated burden, Rbr: 10 MΩ
Rated transformation ratio, Kn: 10 000:1
Rated voltage factor, ku 1.9/8 h
Temperature category
Operation: - 5°C / + 40°C
Transport and storage: -35°C / + 80°C