Place of Origin: | China (Mainland) |
---|---|
Brand Name: | POCASA |
Model Number: | H2KS |
Output Power: | 1 - 200KW |
Output Type: | Single |
Size: | 192mmx460mmx348mm |
Weight: | 31.5Kg |
Input Voltage: | 220VAC |
Output Voltage: | 220VAC |
Type: | DC/AC Inverters |
Output Frequency: | 50/60HZ |
Output Current: | 7A |
Quick Details
Specifications
True sine-wave output with less than 3% THD
Zero transfer/complete isolation of input AC
Powerful true RS232 communication via the enclosed software manages and safely shutdown operating systems.
Powerful multi-stage surge components exceed IEEE requirements.
Allows for remote monitoring and control via www
Worry free battery management. The unit turns itself off after ten seconds to conserve battery power when no power needs are detected.
LED's indicate battery levels
The incorporated LED load indicators allow IT professionals to manage backup time and balance power loads.
The low battery level indicator will warn of eminent UPS shutdown two full minutes before unit shuts down.
A preventative measure that indicates when batteries must be replaced to prevent server crashes.
Model |
H1KS |
H2KS |
H3KS |
|
Rated power |
VA/W |
1KVA/0.7KW |
2KVA/1.4KW |
3KVA/2.1KW |
Input |
Nominal voltage |
220VAC |
||
Voltage range |
115~300VAC |
|||
Frequency range |
46~54Hz(default), user adjustable within 40~60Hz |
|||
Power factor |
0.97 |
|||
Connection |
IEC320-10A inlet |
IEC320-16A inlet |
||
Output |
Voltage |
220VAC±2% |
||
Frequency |
46~54Hz or 50Hz±0.2(line mode) |
|||
Waveform |
Pure sine wave |
|||
Distortion |
3% |
4% |
||
Overload capability |
108%~150% for 30 sec., 150% for 300ms |
|||
Current crest ratio |
3:1 |
|||
Connection |
IEC320*4 |
IEC320*6 |
IEC320*3 and |
|
Battery |
Type |
Sealed, maintenance free, lead-acid |
||
Quantity |
3 pieces |
6 pieces |
8 pieces |
|
Back-up time(full load) |
5 min |
9 min |
5 min |
|
Recharge time |
5 hrs to 90% of capacity after full load discharge |
|||
Bypass |
Automatic transfer |
On overload and UPS failure |
||
Before UPS power-on |
Default " NO" , user adjustable to " YES" |
|||
Voltage range |
80~264VAC(default), user adjustable within 80~286VAC |
|||
Transfer time |
0 ms; less than 4ms from inverter to bypass and vice versa |
|||
LED indicators |
Status |
Load level/battery level, battery , utility power, inverter, bypass, overload, fault |
||
Audible alarm |
Bypass, on battery mode, battery low, overload, fault |
|||
Acoustic noise |
At 1 meter distance |
45 dB |
50 dB |
|
Communication |
DB-9 port |
RS-232 serial interface |
||
Intelligent slot |
Options: Webpower, AS400 card or Winpower CMC |
|||
Network surge protection |
RJ45 I/O port available for network or fax/modem |
|||
Environmental |
Operating temperature |
0~40°C |
||
Operating humidity |
20~90% non-condensing |
|||
Weight |
Net(Kg) |
13 |
31.5 |
32 |
Dimension |
WxDxH(mm) |
145x400x220 |
192x460x348 |