1. General Scope


EMT CO., LTD. Automatic Line Sectionalizers are three-phase devices that automatically open all three phases simultaneously for either phase or ground faults. They are to protect electrical distribution systems by isolating automatically faulted section in conjunction with automatic recloser to minimize SAIDI and SAIFI. Combined with the recloser, EMT sectionalizer detects and counts fault current. After pre-determined number of interruption current, EMT Sectionalizer is able to trip automatically, isolating the faulted section. In addition, EMT Sectionlaizer is able to prevent miscounting or malfunction caused by Inrush current by Inrush restrain function. There are SF6 Gas type, Oil or polymer type Insulated EMT Sectionalizer.



2. Automatic Line Sectionalizer Key Functions


?Automatic Trip after pre-determined counts of faults
?One count trip by trip lever under any fault count set in case of hot line work
?Settable Ground/Phase Fault actuating current Level
?Manual or motorizing operation
?Inrush restrain function to prevent malfunction and miscounting by inrush current
?Optionally can be coordinated in SCADA  system through RTU (or Integrated RTU)



3. General Specification


?Insulation : SF6 Gas (400A, 630 A)  / OIL TYPE  (200A, 400A)
?Arch extinguishing Method
–SF6GAS  Puffer: 12 ~ 35 kV / 400 A, 630 A
–OIL Puffer: 12 ~ 24 kV / 200 A, 400 A
?Maximum Fault Current Interrupting Capability: 900 A