Product Main

Quick Details

Place of Origin: China (Mainland)
Brand Name: ANSUN
Model Number: AM40-220
Nominal working voltage: 220V DC
Nominal discharge current: 20KA
Max discharge current: 40KA
Protection level: 1200V
Dimension: Dimension

Specifications

Safety precautions:

a) When the SPD is installed in final system, it must achieve all the requirements of GB4943 (EN60950, IEC60950) standard;

b) The equipment has to be installed by authorized professional person, before installation, to cut off power supply, and prohibit hot-line work from accidents

c)  The load current of protected equipments should be below 10A, or the product will cut off the power automatically, only to push the black button on   power line terminal to recover

 

Application

AM type DC power SPD is to prevent lightning over-voltage and transient over-voltage from damaging DC power system and equipments, which mainly used in mobile communication base, microwave communication base, telecommunication computer room, factory, airport, finance and securities

Also applied in several DC power system, such as DC distribution board, DC power supply equipment, DC distribution box, electronic information system cabinet and the output terminal of second stage power equipment

 
Features:

1)  Temperature control circuit break technology, built-in over-current protection circuit, to completely keep away from fire disaster

2)   International famous components and advanced manufacturing technique

3)   Big discharger current capacity, low residual voltage

4)   Remote alarm connect point(standard)  

5)   Clear and intuitive working condition

6)   Easy installation and maintain

7)   Exquisite process, can work under the hostile environment for a long time, like acid, alkali, dust, salt fog, wet, etc

 

Specification

 

Model

AM40-220

Nominal operating voltage Un

        220VDC         

Max continuous operating voltage(Uc)

320VDC 

Nominal discharge current(kA)

20KA

Max discharge current(kA)

40kA

Protected level

≤1500V

Response time

≤25ns

flameretardantrating(UL94)

V0

Protection Level

IP20

Telecommand definition

1-2: NC, 2:COM, 2-3: NO

NC-COM: NC, COM:COM, NO-COM: NO

Dimension(mm)

Single connection: 90*18*69mm

double connection: 90*36*69mm

Connecting diameter(mm2)

+/- line: 6 mm2above, ground line: 10 mm2above

Working conditions

Temperature:40~+85℃; Relative humidity:≤95(25); Elevation≤3km

Note: For latest information, please contact ANSUN company

 
Installation

1)  35mm slide guide installation way,

2)   Connect +/- and ground terminal of power system to +/- and ground terminal of SPD, then screw up the bolts

3)   ground line of SPD to lightning protection system ground device

4)   After wiring, please check it until everything is going well, to put into operation.

 Product maintenance

a)  The equipment has to be installed by authorized professional person, before installation, to cut off power supply, and prohibit hot-line work from accidents

b)  The sectional area of wire must reach technical demands

c)   When the SPD box is installed in final system, it must achieve all the requirements of GB4943 (EN60950, IEC60950) standard;

d)   The product does not need to be maintained specially, but to inspect at fixed period

e)   After thunderstorm season, it is normal that the indicator window is red, but to change a new module or total product instantly

f)    Once there is a failure during system operation, please remove the SPD device at first, if the system can operate normally, the device is broken

 

Product standard

IEC61643-1: 1998 Surge Protective devices connected to Low-voltage power

Distribution system.Part1: Performance requirements and testing methods

EN60950: Safety of information technology equipment, including electrical business equipment