Place of Origin: | China (Mainland) |
---|---|
Brand Name: | ANSUN |
Model Number: | AM10-12 |
Nominal working voltage: | 12V DC |
Max working voltage: | 25V |
Nominal discharge current: | 5KA |
Max discharge current: | 10KA |
Dimension: | 90*18*65mm |
Quick Details
Specifications
Application
AM type DC power SPD is to prevent lightning over-voltage and transient over-voltage from damaging DC power system and equipments, which mainly used in mobile communication base, microwave communication base, telecommunication computer room, factory, airport, finance and securities
Also applied in several DC power system, such as DC distribution board, DC power supply equipment, DC distribution box, electronic information system cabinet and the output terminal of second stage power equipment
Features:
1) Temperature control circuit break technology, built-in over-current protection circuit, to completely keep away from fire disaster
2) International famous components and advanced manufacturing technique
3) Big discharger current capacity, low residual voltage
4) Remote alarm connect point(standard)
5) Clear and intuitive working condition
6) Easy installation and maintain
7) Exquisite process, can work under the hostile environment for a long time, like acid, alkali, dust, salt fog, wet, etc
Specification
Model |
AM10-12 |
Nominal operating voltage Un |
12VDC |
Max continuous operating voltage(Uc) |
18 VDC
|
Nominal discharge current(kA) |
5KA |
Max discharge current(kA) |
10kA |
Protected level |
≤150V |
Response time |
≤25ns |
flameretardantrating(UL94) |
V0 |
Protection Level |
IP20 |
Telecommand definition |
1-2: NC, 2:COM, 2-3: NO |
NC-COM: NC, COM:COM, NO-COM: NO |
|
Dimension(mm) |
Single connection: 90*18*69mm double connection: 90*36*69mm |
Connecting diameter(mm2) |
+/- line: 6 mm2above, ground line: 10 mm2above |
Working conditions |
Temperature:-40~+85℃; Relative humidity:≤95%(25℃); Elevation≤3km |