Product Main

Quick Details

Place of Origin: China (Mainland)
Brand Name: ANSUN
Model Number: AJ2D-48
nominal working voltage: 24-48V
nominal discharge current: 5KA
max discharge current: 10KA
protection level: 100V
protected line: 1/2/3/4/5/6/7/8
dimension: 105*53*28mm
transmission speed: 100M/1000M

Specifications

Application

AJ2D-48 type POE SPD, integrated by power SPD and network signal SPD, is mainly used to protect sensitive POE, IP telephone and network surveillance device, from damaging by lightning induced voltage, power interference and electrostatic discharge.

 

Feature

1)   Power+network multi stage protective circuit

2)   International famous core component brand

3)   High discharge current capacity, low insertion loss, superior transmission performance, no leakage current

4)   Low residual voltage, perfect protective effect

5)   Quick response, stable performance, reliable working

6)   Small size, easy installation

 

Specification

 

Product model

AJ2D-48

1. power specification

Max continuous working voltage (Uc)

48VDC

Nominal discharge current (In)

5KA

Max discharge current (In)

10KA

Protection level

≤100V

2. net specification

Max continuous working voltage (Uc)

5V

Nominal discharge current (In)

5KA

Max discharge current (In)

10KA

Protection level

≤25V(core wire—case/ground)

Data transmission rate

100Mbps/1000Mbps

Insertion loss

≤0.5dB

Interface type

RJ45

3. other specification

Case

Aluminum material, oxidation surface(black, silver)

Dimension

112*40*25mm

Wire interface

Power supply

Compression joint port, suitable for 16-26AWG(0.15-1.3mm2) wire

Control signal

net signal

rj45 connector

Ground

Earth wire terminal or 2.5mm2earth wire

Installation

Inside of box or cabinet

Working conditions

Temperature:40~+85℃; Relative humidity:≤95(25); Elevation≤3km

Note: For latest information, please contact ANSUN company

 

Installation and wiring

1)  According to protection demands, the SPD is connected by series between protected devices and signal path, the closer the distance to protected devices, the better the protection effect.

2)  To connect separately a)the cable to the input terminal of power, net , b) output terminal of SPD power, net to related interface of protected devices, c) ground line of SPD to earth wire of lightning protection system

3)   After wiring, please check it until everything is going well, to put into operation.