Place of Origin: | China (Mainland) |
---|---|
Brand Name: | SIHU |
Model Number: | LVQB-66W(1,2or3) |
Usage: | power measurement&relay protection |
Phase: | Single |
Coil Structure: | Toroidal |
Coil Number: | |
Quality warranty: | 18 months |
Insulated material: | GAS SF6 |
Rated voltage: | 66 kV |
Rated primary current: | 50A~4000 A |
Highest voltage for equipment: | 72.5.kV |
Colour: | GREY |
Quick Details
Specifications
Technical Parameters for LVQB-66W(1, 2 or 3)Current Transformers
1 Rated voltage 66 kV
2 Highest voltage for equipment 72.5kV
3 Rated primary current 50A~4000 A
4 Rated secondary current 5 A or 1 A
5 Rated frequency 50 (60) Hz
6 20~50VA (If any other rated output required, We can satisfy it.)
7 Accuracy class and accuracy classes combination
Steady accuracy classes are 0.2S, 0.2, 0.5S, 0.5, 5P, 10P, PR and PX; transient accuracy classes are TPS, TPX, TPY and TPZ. There are 1~7 pcs secondary windings in a CT.
8 Rated operating pressure of the gas SF6 is 0.40 MPa
9 Minimum operating pressure of the gas SF6 is 0.35 MPa
10 Instrument security factor (FS) of measuring class 5 or 10
11 Accuracy limit factor (ALF) of protective class 5, 10, 15, 20, 30 or 40
12 Rated continuous thermal current Icth 1.2In
13 For rated short-time thermal current Ith (rms) and rated dynamic current Idyn (peak), please see Table 1
Table 1
Primary Current (A) |
50~1600 |
2000~4000 |
Rated Short-time Thermal Current (rms) (kA), 3s |
31.5 |
50 |
Rated Dynamic Current (Peak) (kA) |
79 |
125 |
14 Arcing Distance ≥410 (mm)
15 Creepage distance of outer insulation please see Table 2
Table 2
Pollution Protection Class |
Class II (W1) |
Class III (W2) |
Class IV (W3) |
Creepage Distance (mm) |
≥1450 |
≥1813 |
≥2248 |
Notes: Detailed technical data and outline drawing are provided upon request.