| Place of Origin: | China (Mainland) |
|---|---|
| Brand Name: | SIHU |
| Model Number: | LMWSB |
| Usage: | Potential |
| Phase: | Single |
| Coil Structure: | Toroidal |
| Coil Number: | optional |
| Insulated material: | Epoxy resin |
| Quality warranty: | 18 months |
| Rated primary current: | 100-400A |
| Rated primary voltage: | 0.66kV |
| Shell: | stainless steel |
| Dimensions: | customized |
| Rated insulation level: | 0.72 / 3kV |
Quick Details
Specifications
Product Name: Outdoor Bar Type TAT Current Transformer
1 Product instructions
The current transformers are outdoor products of a busbar going thru type, with a metal protective case
(stainless steel or aluminium). Between the case and the case cover, a silicon rubber bar is used for seal and isolation. At the ring direction of case and cover, there is a gap for magnetic isolation, and there is a earthing
bolt on the case and cover correspondingly. It is much suit for going in and out bushing type current
transformer of 66~220kV PASS switchgear.
2 Technical parameters
2.1 Rated insulation level: 0.72 / 3kV.
Notes: Dimension drawings will be provifed under request.
3 Service conditions
3.1 Ambient air temperature: -45 ~ 80℃.
3.2 Altitude: ≤3000 m.
3.3 The average relative humidity in a month: ≤90 %.
3.4 There have to be no gas that may seriously affect the insulation and conductive ability of electric
equipments, steam, ash, salt, chemical deposit, pollution and corrosive or explosive material.
NotesL: Dimension drawings will be provifed under request.
4. Delivery and Packing:
1 Product instructions
The current transformers are outdoor products of a busbar going thru type, with a metal protective case
(stainless steel or aluminium). Between the case and the case cover, a silicon rubber bar is used for seal and isolation. At the ring direction of case and cover, there is a gap for magnetic isolation, and there is a earthing
bolt on the case and cover correspondingly. It is much suit for going in and out bushing type current
transformer of 66~220kV PASS switchgear.
2 Technical parameters
2.1 Rated insulation level: 0.72 / 3kV.
|
Rated Frequency (Hz) |
Rated Primary Current (A) |
Rated Secondary Current (A) |
Accuracy Classes Combination |
Instrument Security Factor |
Rated Output cosΦ=0.8 (VA) |
Rated Voltage (kV) |
|
50 60 |
100-400 |
5 1 |
0.2S 0.2 0.5S 0.5 5P10 5P20 5P30 5P50 5P70 10P10 10P20 10P30 X PX PR TPS TPX TPY TPZ |
≤5 ≤10 ≤15 ≤20 ≤25 |
5~60 |
0.66 |
3 Service conditions
3.1 Ambient air temperature: -45 ~ 80℃.
3.2 Altitude: ≤3000 m.
3.3 The average relative humidity in a month: ≤90 %.
3.4 There have to be no gas that may seriously affect the insulation and conductive ability of electric
equipments, steam, ash, salt, chemical deposit, pollution and corrosive or explosive material.
NotesL: Dimension drawings will be provifed under request.
4. Delivery and Packing:
|
Delivery time: |
20 days |
|
Min. order: |
3 units |
|
Port: |
Guangzhou |
|
Payment: |
T/T or L/C |
|
Packing: |
Wooden case |