Product Main

Quick Details

Place of Origin: China (Mainland)
Brand Name: SIHU
Model Number: JCII (III) -12
Quality warranty: 18 months
Rated primary current: 20-1600A
Rated output: 15-60VA
Rated voltage: 12kV
Insulated material: Epoxy resin
Colour: Brown

Specifications

Product Name: Metering Device Combined Transformer 12kV


Technical Parameters for JCII (III) -12/150(210) - 650(800) Metering Trucks see Table 1~3
Table 1 Main Technical Parameters of CT LZZC3-12Q
Rated Primary Current
(A)
Accuracy Class CombinationRated Output at Relative Accuracy Class Combination
cosΦ=0.8(lag) (VA)
Rated Short-time Thermal Current (r.m.s)
(kA)
Rated Dynamic Current (Peak)
(kA)
Cl. 0.2SCl. 0.5Cl. 10P10
20~2000.2S/10P
0.5/10P
1515157.2~3518~75
315~125055137
1500~160063157.5

Table 2 Technical Parameters of VTs Table 3 Technical Parameters of Fuse

ModelRated Voltage
(kV)
Rated Voltage of Residual
Voltage Winding
(kV)
Rated Output
(VA)
Limit Output
(VA)

ModelRated Voltage
(kV)
Rated
Current
Breaking
Ability
(kA)
PrimarySecondaryCl. 0.2Cl. 0.5Cl. 1XRNP1-3.63.60.3
0.5
1
2
3
50
JDZ19-10RJC
(JDZ19-10RVJC)
100.1
153060350XRNP1-7.27.2
JDZX19-10RJCI,II or III10/√30.1/√30.1/3153060350XRNP1-1212
For residual voltage winding: Accuracy class is 6P, rated output is 50VA.
Notes: Other technical data and outline drawing should be provided under request.