Place of Origin: | China (Mainland) |
---|---|
Brand Name: | SIHU |
Model Number: | JSZFK -6(10)R(II) |
Usage: | Potential |
Phase: | Three |
Coil Structure: | Toroidal |
Coil Number: | |
Quality warranty: | 18 months |
Insulated material: | Epoxy resin |
Rated output: | 20-200VA |
Dimensions: | 490x230x323mm |
Colour: | Brown |
Quick Details
Specifications
Product Name: Three Phases Electric Cast Resin Voltage Transformers
Main Features:
1.All outside parts, such as terminal box and mounting plate, are made of corrosion proof materials.
2. Low partial discharge.
3. Matching different sizes switchgears.
4. Used in voltage measuring and protection, high accuracy.
5. Less maintenance and pollution free.
6. Easily operated and mounted.
7. High mechanical strength and high dielectric strength.
8. Possessing of the performance of anti-ferromagnetic resonance, the product is a three-phase voltage transformer fuse enclosed. If one of the 3 phases in a non-effective earthing system is earthed at different degree and a ferro-magnetic resonace occurs, the secondary winding of relay procection instrument transformer produces a voltage high enough to actuate a relay.
Technical Parameters for JSZFK -6(10)R(II) Voltage transformers
Technical Parameters Table
Main Features:
1.All outside parts, such as terminal box and mounting plate, are made of corrosion proof materials.
2. Low partial discharge.
3. Matching different sizes switchgears.
4. Used in voltage measuring and protection, high accuracy.
5. Less maintenance and pollution free.
6. Easily operated and mounted.
7. High mechanical strength and high dielectric strength.
8. Possessing of the performance of anti-ferromagnetic resonance, the product is a three-phase voltage transformer fuse enclosed. If one of the 3 phases in a non-effective earthing system is earthed at different degree and a ferro-magnetic resonace occurs, the secondary winding of relay procection instrument transformer produces a voltage high enough to actuate a relay.
Technical Parameters for JSZFK -6(10)R(II) Voltage transformers
Technical Parameters Table
Model | Rated Voltage Ratio (kV) | Accuracy Class |
Rated Output* (VA) |
Limit Output (VA) |
JSZK-6(10)R(II) | 6(10)/√3/0.1/√3/0.1/√3/0.1 | 0.2/6P/6P | 50/100/100 | 800 |
0.5/6P/6P | 100/100/100 | |||
1/6P/6P | 200/100/100 | |||
JSZFK-6(10)R(II) | 6(10)/ √3/0.1/√3/0.1/√3/0.1/√3/0.1 | 0.2/0.2/6P/6P | 20/20/100/100 | 400 |
0.2/0.5/6P/6P | 20/30/100/100 | |||
0.5/0.5/6P/6P | 50/50/100/100 |
*Rated
output here refers to the rated output of each pahse for 3-phase
voltage transformers in accordance with standard of GB1207-2006. Rated
output listed in the table only conforms to the values in one among
them.
Notes: Detailed technical data and outline drawing shall be provided under request.