Product Main

Quick Details

Place of Origin: China (Mainland)
Brand Name: Sihu Instrument
Model Number: JDQXF2-150ZHW
Usage: Power
Phase: Single
Coil Structure: Toroidal
Coil Number:
Approvals: IEC60044-2
Rated voltage: 35-220kV
Accuracy Class: 0.2/0.5
Insulated material: Gas SF6
Installation: outdoor or indoor
Colour: White
Quality warranty: 18 months
Port of dispatch: Huangpu

Specifications

Product Name: Single Phase Gas SF6 High Voltage Transformer


1 Instruction
for JDQXF2-150ZHW Voltage Transformers

The single-phase voltage transformers are matching GIS or PASS high voltage switchgears. Their dimensions, technical parameters and service environments can be designed according to the requirements of the clients.


2 Technical Parameters

2.1 Rated primary voltage: 35 kV, 66 kV, 110 kV, 132 kV, 150 kV and 220 kV and so on.

2.2 Rated secondary voltage: 0.1 /√3 kV or 0.11 /√3 kV.

2.3 Rated voltage of residual voltage winding: 0.1kV or 0.11kV.

2.4 Rated frequency and number of phases: 50 Hz or 60 Hz single-phase.

2.5 Voltage ratio, maximum rated output and corresponding accuracy class please see table 1.

Table 1 Voltage Ratio, Maximum Rated Output and Corresponding Accuracy Class Table
 

Voltage Ratio (kV) Accuracy Class and Rated Output (VA)
Secondary 1a-1n Secondary 2a-2n Residual
da-dn
0.2 0.5 0.2 0.5 3P
35 /√3/ 0.1 /√3-0.1 /√3-0.1
66 /√3/ 0.1 /√3-0.1 /√3-0.1
110 /√3/ 0.1 /√3-0.1 /√3-0.1
132 /√3/ 0.1 /√3-0.1 /√3-0.1
150 /√3/ 0.1 /√3-0.1 /√3-0.1
or
220/√3/ 0.1 /√3-0.1 /√3-0.1
75   75   300
50     100
150      
  150   150
  300    

 

2.6 Thermal limit output: 1500VA (each secondary winding).

2.7 Except for limit loaded power factor from 0.8 (lag) to 1, the rest loaded power factor is 0.8 (lag).

2.8 Rated voltage factor and corresponding rated duration: 1.2 continuous, 1.5 30 s.

2.9 Rated pressure of SF6 (20): 0.40 ~ 0.58 MPa.

2.10 Minimum operating pressure of SF6 (20): 0.35 ~ 0.50 MPa.

Notes:

1 Those listed in the table above are the routine parameters, if there is any different parameter required, we can design it according to the technical parameters of the clients.

2 Detailed technical data and outline drawing should be ptovided upon request.