Product Main

Quick Details

Place of Origin: China (Mainland)
Brand Name: ghorit
Model Number: ZN63(VS1)-12
Type: High Voltage
Poles Number: 3
certificate: ISO9001
rated voltage: 12kv
rated frequency: 50hz

Specifications

 ZN63(VS1)-12 Series Handcart Type Indoor Vacuum Circuit Breaker

ZN63(VS1)-12 series indoor vacuum circuit breaker is a three-phase AC 50Hz, rated voltage of 12kV indoor switchgear, control and protection for industrial and mining enterprise, power plants and substations, electrical facilities, and for frequent operation place. Adopting VET operating mechanism and circuit breaker integrated, design can be used as a fixed installation unit can also be equipped with special advance mechanism, the composition of handcart unit used. Some of the main circuit can use the whole solid seal post, in order to achieve smaller circuit breakers, high reliability, maintenance –free, can be equipped with KYN28A-12(GZS) and other handcart switch cabinet in the home can also be used with fixed XGN switchgear.

The Use of Environmental Conditions

1.       Ambient Temperature: not higher than +40, not less than -10 (at -30 to allow storage and transportation).

2.       Altitude: not exceed 1000m.

3.       Relative Humidity: daily average of no more than 95%, saturated vapor pressure daily average of no more than 2.2x10-3 MPa, month average not more than 1.8x10-3 MPa.

4.       Earthquake Intensity: not more than 8.

5.       No fire, explosion hazard, serious filthy, chemical corrosion, as well as place of intense vibration.
 

Mainly Technical Parameters

NO.

Item

Units

Parameters

1

Rated voltage

kV

12

2

Rated insulation level

Rated lightning impulse voltage tolerance

kV

75

1 min frequency voltage

42

3

Rated short-circuit breaking current

kA

20/25

31.5

40

4

Rated current

A

630

1250

630

1600

2500

1250

2000

3150

1250

2000

3150

1600

2500

4000

5

Rated thermal stability of current (RMS)

kA

20/25

31.5

40

6

Dynamic stability rated current (peak)

50/63

80

100

7

Rated short-circuit closing current (peak)

50/63

80

100

8

Rated short-circuit breaking current breaking number

times

500

9

Frequency tolerance of the secondary circuit voltage (1min)

V

2000

10

Rated operating sequence

O-0.3s-CO-180s-CO

O-180s-CO-180s-CO

11

Rated thermal stabilization time

S

12

Rated a single / back-to-back electric current breaking device group

A

630/400 800/400 (40kA)

13

Mechanical life

times

10000