Product Main

Quick Details

Place of Origin: China (Mainland)
Brand Name: ghorit
Model Number: ZN63(VS1)-24
Type: High Voltage
Poles Number: 3
certificate: ISO9001
rated voltage: 24kv
rated frequency: 50hz

Specifications

 ZN63(VS1)-24 Series Handcart Type Indoor Vacuum Circuit Breaker

ZN63(VS1)-24 series handcart type indoor vacuum circuit breaker is rated voltage 24kV, three-phase AC 50Hz indoor high-voltage switchgear, apply for power stations, substations, and industrial and mining enterprises to control or protection transmission and distribution systems, specially for the important high altitude breaking load and frequent operation place.

Circuit breaker manufacturing accordance with our national standard GB1984-2003 (AC high voltage circuit breakers), DL/T403-2000 (3.6~40.5kV indoor vacuum circuit breaker ordering technology); and the related IEC standards and reliable interlock function.

Circuit breaker operating mechanism for the spring energy storage type, can use AC and DC energy storage operations, can also be used manually.

Circuit breaker can be equipped with long life permanent magnetic actuator, mechanical life can reached 60000times, can be used for extremely frequent operation place.

Circuit breaker designed to repackage the structure before and after, both can be used as a fixed installation unit, can also be equipped with the chassis as used in the mounted unit.

The Use of Environmental Conditions

1.  Ambient Temperature: not higher than +40, not less than -15.

2.  Altitude: not exceed 1000m.

3.  Relative Humidity: daily average of not more than 95%, month average of not more than 90%.

4. Earthquake Intensity: not more than 8.

5.  No fire, explosion hazard, serious filthy, chemical corrosion, as well as places of intense vibration.

 

Mainly Technical Parameters

NO.

Item

Units

Parameters

1

Rated voltage

kV

24

2

Rated frequency

Hz

25

3

Rated current

A

42

4

Rated short-circuit breaking current

kA

630, 1250, 1600, 2000, 3150

5

Rated short-circuit closing current (peak)

kA

20, 25, 31.5

6

Rated short-circuit duration

s

50, 63, 80

7

Rated short-circuit breaking current breaking number

Times

4

8

Rated operating sequence

30

9

Rated lightning impulse withstand voltage

kV

O-0.3s-CO-180s-CO

10

1 min power frequency withstand voltage

kV

125

11

Closing time

ms

65

12

Opening time

ms

70

13

Mechanical life

Times

50

14

Rated storage and operation voltage

V

220/110

15

Breaking life

ms

80

16

Storage life

s

10


Adjust the Parameter of Mechanical Properties

NO.

Item

Units

Parameters

1

Contact distance

mm

14±1

2

Contact overtravel

mm

3.5±1

3

Closing speed

m/s

1.0±0.2

4

Opening speed

m/s

1.3±0.2

5

Contact closing spring time

ms

2

6

Rated contact pressure

N

20kA(2400±200) 25kA(2400±200) 31.5kA(3100±200)

7

Three phase closing opening asynchrony

ms

2