Product Main

Quick Details

Place of Origin: China (Mainland)
Brand Name: ghorit
Model Number: GVM6-12
Type: Magnetic
Poles Number: 3
certificate: ISO9002
rated voltage: 12kv
rated frequency: 50hz

Specifications

GVM6-12 Series Permanent Magnet Embedded Poles Type Indoor Vacuum Circuit Breaker

GVM6-12 series permanent magnet embedded poles type indoor vacuum circuit breaker is a three-phase AC 50Hz, rated voltage of 12kV indoor switchgear. I loaded the company with its own research and development of permanent magnetic actuator for industrial and mining enterprises, power generation and substation facilities as electrical control and protection purpose. The product has high reliability and long life characteristics, especially suitable for frequent operation, repeatedly breaking conditions, such as short-circuit current of the place.

Note: this models vacuum interrupter chamber seal replaced with ordinary insulation tube column installation method, the model GVM6-12P.

Main Features

1.High reliability, long life, maintenance-free.

2. China's first permanent magnetic actuator mechanical life of up 100,000 times.

3.With the traditional actuator compared without mechanical removal, locking devices, parts and components significantly reduced the number of hours worked with only one moving parts, low failure rate.

4. Actuator performance and interrupter breaking. Closing the features needed for a very consistent.

5. All sub-reliable operation of the bistable gate.

6.With anti-skip function.

7. With controlling power low-voltage alarm refuse to close

8.Mechanical manual sub-sub-gate and electric gate at the same rate, in the secondary power supply fault conditions, the application of an emergency sub-gate.

9. AC and DC energy storage operation type, operating current is less than 2A, can be done o-co-o operation within 2 hours after the blackout.

10. Highly reliable operation of control circuit module that can be tolerated in the run-time lighting, surge and other harsh conditions.

11. Versatility, installation size and ZN63 VS1 compatible with other products.

The Use of Environmental Conditions

1. Ambient Temperature: not higher than +40 Celsius, not less than -25 Celsius.

2. Altitude: not exceed 1000m, plateau type not exceed 3000m.

3. Relative Humidity: daily average is not more than 95%, month average is not more than 90%, statured vapor pressure daily average is not more than 2.2x10-3 MPa, month average is not more that 1.8x10-3 MPa. The temperature dropped rapidly during the period of high humidity is that it may gel.

4. Earthquake Intensity: not more than 8.

5. No fire, explosion hazard, serious filthy, chemical corrosion, as well as places of intense vibration.

 

Mainly Technical Parameters 

NO.

Item

Units

Parameters

1

Rated voltage

kV

12

2

Rated insulation level

1 min frequency voltage

75

Rated lightning impulse voltage tolerance

42

3

Rated current

A

630-1250

1250-3150

1250-4000*

4

Rated short-circuit breaking current

kA

20

31.5

40

5

Rated short-circuit closing current (peak)

50

80

100

6

Dynamic stability rated current (peak)

50

80

100

7

Rated thermal stability of current (RMS)

20

51.5

40

8

Rated short-circuit breaking current breaking number

Times

30

30

20

9

Rated thermal stabilization time

S

4

10

Rated operating sequence

O-0.3s-CO-180s-CO

11

Mechanical life

Times

500050003000**

12

Permanent magnetic actuator and transmission part of the mechanical life

Times

≥100000≥100000≥100000

13

Rated single capacitor breaking current

A

630

14

Rated back to back capacitor breaking current

400

15

Rated breaking current-step

kA

12.6      16

*There should be greater than the rated current 3150A ventilation measures.

**According to the chosen vacuum interrupter and the disparity.


Adjust the Parameters of Mechanical Properties 

NO.

Item

Units

Parameters

1

Contact distance

mm

11±1*

2

Contact travel

3.5±0.5

3

Three phase opening synchronism

ms

≤2

4

Contact closing spring time

≤2     ≤3(40kA)

5

Phases center distance

mm

210        275

6

Closing contact pressure

N

20Ka      31.5kA     40kA

2000±200 3100±200 4500±300

7

Leading electrical circuit resistance

υΩ

60          45          30

8

Average opening speed

m/s

1.1±0.2

9

Average closing speed

0.7±0.2    0.8±0.2

10

Opening time

ms

30~60

11

Closing time

50~100

12

Action static contact cumulative wear thickness allows

mm

3