Product Main

Quick Details

Place of Origin: China (Mainland)
Brand Name: ghorit
Model Number: ZN63 (VS1)-12
Type: High Voltage
Poles Number: 3
certificate: ISO9001
rated voltage: 12kv

Specifications

ZN63 (VS1)-12 Series Embedded Poles Type Indoor HV Vacuum Circuit Breaker

ZN63 (VS1)-12 Series Embedded Poles Type Indoor HV Vacuum Circuit Breaker, adopt solid insulation structure; use of advanced solid epoxy sealing technology, the first time, the vacuum interrupter. A leading electrical circuit, insulation and other support to become an integrated combination of solid seal pole. Successfully from a fundamental solution of the vacuum breaker gas environment, tolerance issues, make it broader. Integrated solid-pole closure of the fluent use of a self-ventilation technology cleverly solved the structure of solid insulation caused by heat dissipation.

 ZN63 (VS1)-12 Series Embedded Poles Type Indoor HV Vacuum Circuit Breaker is the first to achieve maintenance-free concept of a circuit breaker. Its high-life vacuum interrupter chamber as well as solid cast epoxy sealing technology applications to ensure an integrated solid-pole sealed maintenance-free, with high reliability using permanent magnetic actuator of the actuator to ensure maintenance-free, electronic control parts reject the traditional auxiliary switch and replaced by photoelectric proximity switches, and use the whole power and intelligent electronic control unit ensures that electronically controlled part of the maintenance-free.

The Use of Environmental Conditions

1. Ambient temperature: not higher than +40 Celsius, not less than -15 Celsius (at -30 Celsius to allow storage and transportation).

2. Altitude: not exceed 1000m.

3. Relative humidity: daily average of not more than 90%, month average of not more than 90%, saturated vapor pressure daily average of not more than 2.2 × 10-3MPa, month average not more than 1.8 × 10-3MPa.

4. Earthquake intensity: not more than 8.

5. No fire, explosion hazard, serious filthy, chemical corrosion, as well as places of intense vibration.

 

Mainly Technical Parameters

NO

Item

Units

parameters

1

Rated voltage

KV

12

2

Rated insulation level

Rated Lightning Impulse voltage tolerance

KV

75

1min Frequency voltage

42

3

Rated short-circuit breaking current

KA

20/25

31.5

40

4

Rated current

A

630

1250

630 1250

1600 2000

2500 3150

1250 1600

2000 2500

3150 4000

5

Rated thermal stability of current (RMS)

KA

20/25

31.5

40

6

Dynamic Stability rated current (peak)

63

80

100

7

Rated short-circuit closing current (peak)

63

80

100

8

Rated short-circuit breaking current breaking number

times

50

9

Frequency tolerance of the secondary circuit voltage (1min)

V

2000

10

Rated operating sequence

0-0.3s-CO-180s-CO 0-180s-CO-180s-CO

11

Rated thermal stabilization time

S

4

12

Rated a single / back-to-back electric current breaking device group

630/400  800/400(40KA)

13

Mechanical life

Times

10000